Comparative Analysis of Symmetrical-Component Extraction Methods for IEEE 2800-2022-Compliant Negative-Sequence Regulation in VSM-Based Grid-Forming Inverters

This paper compares four extraction methods behind an identical interface in a full-order virtual synchronous machine (VSM) grid-forming inverter: the dual second-order generalized integrator with frequency-locked loop (DSOGI-FLL), delayed signal cancellation (DSC), the extended Kalman filter (EKF) and a super-twisting sliding-mode observer (ST-SMO). Simulations cover short-circuit ratios (SCR) of 1.5, 3 and 5, four fault types and three fault profiles at a converged step of 50 microseconds, and are checked against an analytic truth, a negative-sequence reference reconstructed offline, and a step-size study. DSOGI-FLL has the smallest estimation error (median angle error 1.0 degrees against 3.3, 5.2 and 14 degrees for the EKF, DSC and ST-SMO) and the lowest output ripple (median 0.003 pu against 0.016 pu for DSC). Recovery time (median spread 0.01 s) and rotor-angle deviation (at most 2 degrees) are set by the VSM, the fault type and the SCR and not by the extractor. The ST-SMO injection loop oscillates after fault clearing at the gain at which the other methods are stable, so it is run at a lower gain with a nearly inactive injection. Compliance to the IEEE Standard 2800-2022 is assessed on the realized current, because the commanded lead does not determine it.

Authors

Institutions

Publication Details

Published
2026-11-08
DOI
https://doi.org/10.31224/8737
Primary Topic
Microgrid Control and Optimization
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
preprint

Comparative Analysis of Symmetrical-Component Extraction Methods for IEEE 2800-2022-Compliant Negative-Sequence Regulation in VSM-Based Grid-Forming Inverters

Elochukwu Ihekerem
1 links
Microgrid Control and Optimization
preprint

Comparative Analysis of Symmetrical-Component Extraction Methods for IEEE 2800-2022-Compliant Negative-Sequence Regulation in VSM-Based Grid-Forming Inverters

Elochukwu Ihekerem
preprint en

Abstract

This paper compares four extraction methods behind an identical interface in a full-order virtual synchronous machine (VSM) grid-forming inverter: the dual second-order generalized integrator with frequency-locked loop (DSOGI-FLL), delayed signal cancellation (DSC), the extended Kalman filter (EKF) and a super-twisting sliding-mode observer (ST-SMO). Simulations cover short-circuit ratios (SCR) of 1.5, 3 and 5, four fault types and three fault profiles at a converged step of 50 microseconds, and are checked against an analytic truth, a negative-sequence reference reconstructed offline, and a step-size study. DSOGI-FLL has the smallest estimation error (median angle error 1.0 degrees against 3.3, 5.2 and 14 degrees for the EKF, DSC and ST-SMO) and the lowest output ripple (median 0.003 pu against 0.016 pu for DSC). Recovery time (median spread 0.01 s) and rotor-angle deviation (at most 2 degrees) are set by the VSM, the fault type and the SCR and not by the extractor. The ST-SMO injection loop oscillates after fault clearing at the gain at which the other methods are stable, so it is run at a lower gain with a nearly inactive injection. Compliance to the IEEE Standard 2800-2022 is assessed on the realized current, because the commanded lead does not determine it.

Landmark University (NG)
Industry, innovation and infrastructure
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon