Experimental and finite element analysis of coupled electro-thermal responses of concrete-encased grounding electrodes under lightning impulses

Grounding systems are critical for maintaining the safety and transient stability of high-voltage and smart-grid infrastructure subjected to lightning-current impulses. This study presents an integrated experimental and three-dimensional finite element method (FEM) investigation of conventional copper-bonded steel rod and concrete-encased grounding electrodes under standardized 8/20 µs impulse-current conditions. Laboratory experiments were conducted using an impulse-current generator with a maximum current capability of 1.5 kA, while a COMSOL Multiphysics model was developed and validated against the experimentally accessible current range and subsequently used to investigate higher-current conditions numerically. Three representative soil types of clay, sandy loam, and gravel were considered to evaluate transient impedance, ground potential rise (GPR), current-density distribution, soil-ionization behavior, and electro-thermal response. Experimentally, the concrete-encased configuration reduced impulse impedance by approximately 33–49% across the investigated soils. FEM analysis showed a reduction in peak current density from 69 to 43 A/m², corresponding to approximately 38%, together with a larger effective current-conduction region. Numerical predictions at higher current levels indicated delayed soil-ionization onset and lower temperature rise for the encased configuration compared with the conventional rod. These high-current results are identified as FEM predictions rather than direct experimental measurements because they exceed the 1.5 kA capability of the laboratory generator. The validated experimental numerical framework demonstrates the potential of conductive concrete encasement to improve impulse-current dispersion and reduce localized electrical and thermal stress in grounding electrodes. Further high-current experimental validation is required to confirm the predicted behavior beyond the laboratory test range.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2026-11-07
DOI
https://doi.org/10.1038/s41598-026-80007-0
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Experimental and finite element analysis of coupled electro-thermal responses of concrete-encased grounding electrodes under lightning impulses

Asif Irshad Khan, Talal Alqahtani, H.T. Zubair, Md Tanjil Sarker et al.
1 links
Scientific Reports
Lightning and Electromagnetic Phenomena
article

Experimental and finite element analysis of coupled electro-thermal responses of concrete-encased grounding electrodes under lightning impulses

Asif Irshad Khan, Talal Alqahtani, H.T. Zubair, Md Tanjil Sarker, Salem A. Algarni
article en

Abstract

Grounding systems are critical for maintaining the safety and transient stability of high-voltage and smart-grid infrastructure subjected to lightning-current impulses. This study presents an integrated experimental and three-dimensional finite element method (FEM) investigation of conventional copper-bonded steel rod and concrete-encased grounding electrodes under standardized 8/20 µs impulse-current conditions. Laboratory experiments were conducted using an impulse-current generator with a maximum current capability of 1.5 kA, while a COMSOL Multiphysics model was developed and validated against the experimentally accessible current range and subsequently used to investigate higher-current conditions numerically. Three representative soil types of clay, sandy loam, and gravel were considered to evaluate transient impedance, ground potential rise (GPR), current-density distribution, soil-ionization behavior, and electro-thermal response. Experimentally, the concrete-encased configuration reduced impulse impedance by approximately 33–49% across the investigated soils. FEM analysis showed a reduction in peak current density from 69 to 43 A/m², corresponding to approximately 38%, together with a larger effective current-conduction region. Numerical predictions at higher current levels indicated delayed soil-ionization onset and lower temperature rise for the encased configuration compared with the conventional rod. These high-current results are identified as FEM predictions rather than direct experimental measurements because they exceed the 1.5 kA capability of the laboratory generator. The validated experimental numerical framework demonstrates the potential of conductive concrete encasement to improve impulse-current dispersion and reduce localized electrical and thermal stress in grounding electrodes. Further high-current experimental validation is required to confirm the predicted behavior beyond the laboratory test range.

Scientific Reports
Aligarh Muslim University (IN), Multimedia University (MY), King Khalid University (SA)
King Khalid University
Openalex Percentile: Top 26%
Lightning and Electromagnetic Phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon