Overheating Characteristics of Contact Defects in the Transition Circuit of Oil-immersed Power Transmission Equipment On-Load Tap Changer

Abstract To address the local overheating and ablation problems of fastening connection structures in the transition circuit of oil-immersed power transmission equipment on-load tap changers (OLTCs), this paper proposes a contact-defect simulation method based on Joule-heating energy equivalence. According to the short-duration high-current characteristics during tap-changing operation, the current-carrying process of the transition circuit is equivalently converted into a laboratory current-carrying condition of 258 A for 2 s. A temperature-rise test platform consisting of a programmable AC constant-current source, prototype connection specimens, and an infrared thermal imager is established. Typical contact-defect conditions, including insufficient tightening torque, foreign-particle inclusion, abnormal anti-loosening coating, and uneven contact end surfaces, are designed to investigate the temperature-rise characteristics of the connection structure. The experimental results show that contact defects change the contact state of the conductor-connector interface, reduce the real contact area, increase the contact resistance, and intensify local temperature rise. Furthermore, an electro-thermal coupled simulation model is developed, in which an equivalent contact heat flux is used to characterize the additional interfacial heating caused by contact degradation. The results show that when the equivalent contact heat flux increases from 1.0×105 W/m2 to 1.0×106 W/m2, the simulated additional temperature rise increases from 9.07 ℃ to 103.06 ℃, which is consistent with the experimental trend that contact defects lead to increased temperature rise. The results can provide a reference for assembly quality control and overheating-defect diagnosis of transition circuits in oil-immersed power transmission equipment OLTCs.

Authors

Institutions

Publication Details

Journal
Engineering Research Express
Published
2026-11-06
DOI
https://doi.org/10.1088/2631-8695/aebf2e
Primary Topic
Electrical Contact Performance and Analysis
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Overheating Characteristics of Contact Defects in the Transition Circuit of Oil-immersed Power Transmission Equipment On-Load Tap Changer

Jiahao Li, Hong Liu, Shuaibiao Zeng, Jiayi Guo et al.
Engineering Research Express
Electrical Contact Performance and Analysis
article

Overheating Characteristics of Contact Defects in the Transition Circuit of Oil-immersed Power Transmission Equipment On-Load Tap Changer

Jiahao Li, Hong Liu, Shuaibiao Zeng, Jiayi Guo, Hua Yu
article en

Abstract

Abstract To address the local overheating and ablation problems of fastening connection structures in the transition circuit of oil-immersed power transmission equipment on-load tap changers (OLTCs), this paper proposes a contact-defect simulation method based on Joule-heating energy equivalence. According to the short-duration high-current characteristics during tap-changing operation, the current-carrying process of the transition circuit is equivalently converted into a laboratory current-carrying condition of 258 A for 2 s. A temperature-rise test platform consisting of a programmable AC constant-current source, prototype connection specimens, and an infrared thermal imager is established. Typical contact-defect conditions, including insufficient tightening torque, foreign-particle inclusion, abnormal anti-loosening coating, and uneven contact end surfaces, are designed to investigate the temperature-rise characteristics of the connection structure. The experimental results show that contact defects change the contact state of the conductor-connector interface, reduce the real contact area, increase the contact resistance, and intensify local temperature rise. Furthermore, an electro-thermal coupled simulation model is developed, in which an equivalent contact heat flux is used to characterize the additional interfacial heating caused by contact degradation. The results show that when the equivalent contact heat flux increases from 1.0×105 W/m2 to 1.0×106 W/m2, the simulated additional temperature rise increases from 9.07 ℃ to 103.06 ℃, which is consistent with the experimental trend that contact defects lead to increased temperature rise. The results can provide a reference for assembly quality control and overheating-defect diagnosis of transition circuits in oil-immersed power transmission equipment OLTCs.

Engineering Research Express
North China Electric Power University (CN), State Grid Shanxi Electric Power Company Electric Power Research Institute (CN)
Openalex Percentile: Top 25%
Electrical Contact Performance and Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon