Experimental Study of Non-Design-Basis Electromagnetic Interference and the Risk of False Operation of Relay Protection at a 500 kV Substation

Cascading failures in power systems worldwide are often triggered by short-circuit (SC) faults accompanied by intense high-frequency (HF) electromagnetic transients that can generate non-design-basis electromagnetic interference (EMI) and increase the risk of maloperation of microprocessor-based relay protection and automation (RPA) devices. This paper presents an on-site simulation method for determining the level of HF antiphase EMI in RPA control circuits, based on reproducing the HF component of the short-circuit current using a pulse generator with test current injection into the grounding system. The method was validated at the operating 500 kV Shymkent substation of KEGOC JSC (Republic of Kazakhstan): pulsed electromagnetic disturbances in secondary circuits were measured at the 500 kV and 220 kV switchyards while simulating the HF component of the single-phase-to-ground short-circuit current. It was experimentally established that the level of induced antiphase interference is determined by the impulse resistance of the grounding system and the attenuation coefficient of the disturbance into secondary circuits, and in a number of the investigated circuits the levels rescaled to the HF component of the fault current exceed the 1 kV immunity test level of microprocessor-based devices. The measured impulse resistance of the equipment grounding was 1.8–7.2 Ω, the attenuation coefficient was 2.1–12.7, and the rescaled differential-mode interference reached 1.9 kV (1.5–2.2 kV, taking into account an uncertainty of ±20%). Since the reaction of the terminals was not recorded, these results indicate an increased risk of RPA maloperation due to non-design-basis EMI during short circuits and justify the need to account for this factor when designing grounding systems and configuring relay protection settings.

Authors

Institutions

Publication Details

Journal
Applied Sciences
Published
2026-11-05
DOI
https://doi.org/10.3390/app162110946
Primary Topic
Electromagnetic Compatibility and Noise Suppression
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Experimental Study of Non-Design-Basis Electromagnetic Interference and the Risk of False Operation of Relay Protection at a 500 kV Substation

S. S. Dautov, M. S. Zharmagambetova, Zhansulu Ualieva, Akzhol Sauranbayev et al.
Applied Sciences
Electromagnetic Compatibility and Noise Suppression
article

Experimental Study of Non-Design-Basis Electromagnetic Interference and the Risk of False Operation of Relay Protection at a 500 kV Substation

S. S. Dautov, M. S. Zharmagambetova, Zhansulu Ualieva, Akzhol Sauranbayev, Bekmukhambet Kangozhin
article en

Abstract

Cascading failures in power systems worldwide are often triggered by short-circuit (SC) faults accompanied by intense high-frequency (HF) electromagnetic transients that can generate non-design-basis electromagnetic interference (EMI) and increase the risk of maloperation of microprocessor-based relay protection and automation (RPA) devices. This paper presents an on-site simulation method for determining the level of HF antiphase EMI in RPA control circuits, based on reproducing the HF component of the short-circuit current using a pulse generator with test current injection into the grounding system. The method was validated at the operating 500 kV Shymkent substation of KEGOC JSC (Republic of Kazakhstan): pulsed electromagnetic disturbances in secondary circuits were measured at the 500 kV and 220 kV switchyards while simulating the HF component of the single-phase-to-ground short-circuit current. It was experimentally established that the level of induced antiphase interference is determined by the impulse resistance of the grounding system and the attenuation coefficient of the disturbance into secondary circuits, and in a number of the investigated circuits the levels rescaled to the HF component of the fault current exceed the 1 kV immunity test level of microprocessor-based devices. The measured impulse resistance of the equipment grounding was 1.8–7.2 Ω, the attenuation coefficient was 2.1–12.7, and the rescaled differential-mode interference reached 1.9 kV (1.5–2.2 kV, taking into account an uncertainty of ±20%). Since the reaction of the terminals was not recorded, these results indicate an increased risk of RPA maloperation due to non-design-basis EMI during short circuits and justify the need to account for this factor when designing grounding systems and configuring relay protection settings.

Applied SciencesVol. 16(21)
Mukhametzhan Tynyshbayev ALT University (KZ)
Openalex Percentile: Top 25%
Electromagnetic Compatibility and Noise Suppression
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon