Performance of AC systems under future climates and heatwaves: From degradation to temperature regime optimization and dehumidification control

Rising outdoor temperatures and the increasing frequency of heatwaves raise pressing challenges to the resilience of building cooling systems, particularly in tropical regions where cooling demand is continuous, and dehumidification is essential. This study investigates the impact of future climate scenarios, including typical meteorological years and heatwave years provided by the International Energy Agency’s Annex 80, on the seasonal performance of conventional vapor-compression cooling systems: unitary systems, represented by split units. Numerical simulations were carried out using EnergyPlus to assess the Seasonal Coefficient of Performance (SCOP). Results indicate that split systems performance and optimal sizing strategies are sensitive to climate change, with SCOP degradation between 5% and 10% by the end of the century and up to 12% during severe heatwaves. In contrast, centralized chilled-water systems exhibit greater adaptability through temperature regime optimization. Raising the chilled-water supply temperature by several degrees reduces the refrigerant lift and distribution thermal losses, improving chiller SCOP by up to 5%. However, these benefits come at the expense of reduced dehumidification capacity, highlighting a fundamental balance between energy efficiency and hygrometric comfort. Overall, the results highlight the importance of considering future climate conditions when assessing air-conditioning performance and suggest that elevated chilled-water temperature regimes can improve system efficiency while remaining compatible with thermal and hygrometric comfort within a case-specific operating range. For the simulated chilled-water configuration, higher supply temperatures improved energy performance while maintaining acceptable indoor conditions up to system- and comfort-dependent limits.

Authors

Institutions

Publication Details

Journal
Energy Reports
Published
2026-11-04
DOI
https://doi.org/10.1016/j.egyr.2026.109895
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance of AC systems under future climates and heatwaves: From degradation to temperature regime optimization and dehumidification control

Jean-Francois Martin, Franck Lucas, Kanhan Sanjivy, Olivier Marc et al.
Energy Reports
Building Energy and Comfort Optimization
article

Performance of AC systems under future climates and heatwaves: From degradation to temperature regime optimization and dehumidification control

Jean-Francois Martin, Franck Lucas, Kanhan Sanjivy, Olivier Marc, Pierre Steinmetz
article en

Abstract

Rising outdoor temperatures and the increasing frequency of heatwaves raise pressing challenges to the resilience of building cooling systems, particularly in tropical regions where cooling demand is continuous, and dehumidification is essential. This study investigates the impact of future climate scenarios, including typical meteorological years and heatwave years provided by the International Energy Agency’s Annex 80, on the seasonal performance of conventional vapor-compression cooling systems: unitary systems, represented by split units. Numerical simulations were carried out using EnergyPlus to assess the Seasonal Coefficient of Performance (SCOP). Results indicate that split systems performance and optimal sizing strategies are sensitive to climate change, with SCOP degradation between 5% and 10% by the end of the century and up to 12% during severe heatwaves. In contrast, centralized chilled-water systems exhibit greater adaptability through temperature regime optimization. Raising the chilled-water supply temperature by several degrees reduces the refrigerant lift and distribution thermal losses, improving chiller SCOP by up to 5%. However, these benefits come at the expense of reduced dehumidification capacity, highlighting a fundamental balance between energy efficiency and hygrometric comfort. Overall, the results highlight the importance of considering future climate conditions when assessing air-conditioning performance and suggest that elevated chilled-water temperature regimes can improve system efficiency while remaining compatible with thermal and hygrometric comfort within a case-specific operating range. For the simulated chilled-water configuration, higher supply temperatures improved energy performance while maintaining acceptable indoor conditions up to system- and comfort-dependent limits.

Energy ReportsVol. 16
École Centrale de Nantes (FR), University of Reunion Island (RE), Géopôle du Pacifique Sud (PF), École Polytechnique Fédérale de Lausanne (CH), University of French Polynesia (PF)
Openalex Percentile: Top 18%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon