Climate-Adapted Lean Six Sigma for Maintenance Improvement in Petrochemical Operations: A Longitudinal Case Study of Cooling-Water Pumps

Maintenance rules in Gulf process plants often come from manufacturer documents written for milder climates. This explanatory case study asks why such a rule persists and what a Lean Six Sigma Define–Measure–Analyse–Improve–Control (DMAIC) project needs to catch it. The case covers 36 months for four American Petroleum Institute (API) 610 cooling-water pumps at a Saudi petrochemical plant, using 47 failure events, 312 work orders, bearing temperature logs and 15 interviews. The dominant failure mode, bearing distress, traced to a quarterly re-lubrication rule fixed in 2015 and applied with a mineral-oil grease. Adopting the bearing makers’ criterion that grease life halves for every 15 °C above 70 °C, an operating-envelope audit showed each summer interval aged the grease two to three times faster than at 70 °C, and eight of eleven baseline bearing events fell in June to September (p = 0.009). After the grade, quantity and interval basis were changed, bearing events fell more than other modes, bearing sets issued fell from nine to three, and summer corrective labour fell from 31 to 9 h. The new 2000 h interval is not supported at peak temperature, so a summer limit is added. The single-site design cannot estimate effect size.

Authors

Institutions

Publication Details

Journal
Sustainability
Published
2026-11-02
DOI
https://doi.org/10.3390/su182111159
Primary Topic
Reliability and Maintenance Optimization
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Climate-Adapted Lean Six Sigma for Maintenance Improvement in Petrochemical Operations: A Longitudinal Case Study of Cooling-Water Pumps

Walid Mahmoud Shewakh, Abdulrahman Mohammed Albar
Sustainability
Reliability and Maintenance Optimization
article

Climate-Adapted Lean Six Sigma for Maintenance Improvement in Petrochemical Operations: A Longitudinal Case Study of Cooling-Water Pumps

Walid Mahmoud Shewakh, Abdulrahman Mohammed Albar
article en

Abstract

Maintenance rules in Gulf process plants often come from manufacturer documents written for milder climates. This explanatory case study asks why such a rule persists and what a Lean Six Sigma Define–Measure–Analyse–Improve–Control (DMAIC) project needs to catch it. The case covers 36 months for four American Petroleum Institute (API) 610 cooling-water pumps at a Saudi petrochemical plant, using 47 failure events, 312 work orders, bearing temperature logs and 15 interviews. The dominant failure mode, bearing distress, traced to a quarterly re-lubrication rule fixed in 2015 and applied with a mineral-oil grease. Adopting the bearing makers’ criterion that grease life halves for every 15 °C above 70 °C, an operating-envelope audit showed each summer interval aged the grease two to three times faster than at 70 °C, and eight of eleven baseline bearing events fell in June to September (p = 0.009). After the grade, quantity and interval basis were changed, bearing events fell more than other modes, bearing sets issued fell from nine to three, and summer corrective labour fell from 31 to 9 h. The new 2000 h interval is not supported at peak temperature, so a summer limit is added. The single-site design cannot estimate effect size.

SustainabilityVol. 18(21)
Jazan University (SA)
Jazan University
Openalex Percentile: Top 15%
Reliability and Maintenance Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon