The regulation and control process of large hydroelectric generating units under PFR-AGC coordination

Abstract With the increasing penetration of large-scale hydropower bases and long-distance AC/DC transmission, dispatching agencies are applying stricter assessment indices to primary frequency regulation (PFR) and automatic generation control (AGC). In practice, some stations improve the measured response speed by increasing governor sensitivity or shortening command-conversion time constants. Although this may raise short-term performance indicators, it can also enlarge reverse power regulation, reduce damping in the ultra-low-frequency band, and aggravate grid-frequency deterioration after disturbances. To clarify this contradiction, this paper investigates the regulation and control process of large hydroelectric generating units under coordinated PFR-AGC operation. First, the command-generation logic of plant-level AGC, the autonomous droop response of PFR, and their co-control relationship are analyzed. A linearized dynamic model including the water conveyance system, hydraulic turbine, governor, and generator is then established and verified by load rejection and PFR operating records. Based on the validated model, the effects of water-flow inertia constant, pressure-regulation-well coefficient, PWM pulse period, integral conversion parameter, permanent slip coefficient, and governor PID parameters are compared through time-domain simulation and eigenvalue analysis. The results show that excessive pursuit of response speed increases reverse regulation and may move characteristic roots toward the right half-plane. Optimizing PI parameters can reshape the amplitude-frequency and phase-frequency characteristics of the speed control system and suppress ultra-low-frequency oscillation, but a certain reduction in PFR regulating speed should be accepted. The study provides a practical tuning logic for balancing frequency regulation performance and grid stability.

Authors

Institutions

Publication Details

Journal
Engineering Research Express
Published
2026-10-30
DOI
https://doi.org/10.1088/2631-8695/aebc14
Primary Topic
Frequency Control in Power Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The regulation and control process of large hydroelectric generating units under PFR-AGC coordination

Yousong Shi, Xueli An, Zhong Yang, Jian Cheng et al.
2 links
Engineering Research Express
Frequency Control in Power Systems
article

The regulation and control process of large hydroelectric generating units under PFR-AGC coordination

Yousong Shi, Xueli An, Zhong Yang, Jian Cheng, Jinghui Su, Yinbin Li
article en

Abstract

Abstract With the increasing penetration of large-scale hydropower bases and long-distance AC/DC transmission, dispatching agencies are applying stricter assessment indices to primary frequency regulation (PFR) and automatic generation control (AGC). In practice, some stations improve the measured response speed by increasing governor sensitivity or shortening command-conversion time constants. Although this may raise short-term performance indicators, it can also enlarge reverse power regulation, reduce damping in the ultra-low-frequency band, and aggravate grid-frequency deterioration after disturbances. To clarify this contradiction, this paper investigates the regulation and control process of large hydroelectric generating units under coordinated PFR-AGC operation. First, the command-generation logic of plant-level AGC, the autonomous droop response of PFR, and their co-control relationship are analyzed. A linearized dynamic model including the water conveyance system, hydraulic turbine, governor, and generator is then established and verified by load rejection and PFR operating records. Based on the validated model, the effects of water-flow inertia constant, pressure-regulation-well coefficient, PWM pulse period, integral conversion parameter, permanent slip coefficient, and governor PID parameters are compared through time-domain simulation and eigenvalue analysis. The results show that excessive pursuit of response speed increases reverse regulation and may move characteristic roots toward the right half-plane. Optimizing PI parameters can reshape the amplitude-frequency and phase-frequency characteristics of the speed control system and suppress ultra-low-frequency oscillation, but a certain reduction in PFR regulating speed should be accepted. The study provides a practical tuning logic for balancing frequency regulation performance and grid stability.

Engineering Research Express
China Institute of Water Resources and Hydropower Research (CN)
Industry, innovation and infrastructure, Affordable and clean energy
Openalex Percentile: Top 24%
Frequency Control in Power Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon