Orientation-dominated mould risk and hygrothermal remediation in bio-based internally insulated masonry walls: In-situ monitoring and calibrated simulation in an oceanic climate

Insulating a heritage masonry wall from the inside is often the only option when the façade must be preserved — and it is also the most likely to fail, because it traps moisture where the insulation meets the wall. Which bio-based systems survive this, and on which façades, is still poorly understood in oceanic climates. To find out, four bio-based systems — hemp–lime concrete, cellulose wadding, sheep wool and flax wool — were installed on the four differently oriented façades of a historic brick building in northern France and monitored for a year at the insulation–masonry interface, and mould risk was assessed with the extended VTT model. The three fibrous walls had near-identical U-values (0.099–0.107 W·m⁻²·K⁻¹) and thermal masses (567–575 kJ·m⁻²·K⁻¹), and almost identical interface vapour pressures. Differences in their mould response can therefore be attributed mainly to orientation rather than to the insulation material. Their mould indices ranged from below 1 to above 3: colder north-facing interfaces held the relative humidity high enough for mould, while sunnier façades stayed dry. The north-west flax-wool wall spent 256 days above 90% relative humidity and reached a mould index above 3; the south-east hemp–lime wall averaged 69% and stayed below 0.3. This failing wall was reproduced in a calibrated heat-and-moisture model and six corrective measures were tested over three simulated years. The most effective was counter-intuitive: removing the smart vapour retarder — a layer meant to control moisture — was the only measure that brought the mould index back to zero. Thinner insulation helped by warming the interface, while a vapour barrier, thicker insulation, or a hemp–lime replacement all made things worse. The result is orientation-specific guidance for using bio-based internal insulation safely in oceanic climates.

Authors

Institutions

Publication Details

Journal
Case Studies in Construction Materials
Published
2026-10-28
DOI
https://doi.org/10.1016/j.cscm.2026.e06673
Primary Topic
Hygrothermal properties of building materials
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Orientation-dominated mould risk and hygrothermal remediation in bio-based internally insulated masonry walls: In-situ monitoring and calibrated simulation in an oceanic climate

Emmanuel Antczak, Didier Defer, Franck Brachelet, Machhour EL ASSAAD
2 links
Case Studies in Construction Materials
Hygrothermal properties of building materials
article

Orientation-dominated mould risk and hygrothermal remediation in bio-based internally insulated masonry walls: In-situ monitoring and calibrated simulation in an oceanic climate

Emmanuel Antczak, Didier Defer, Franck Brachelet, Machhour EL ASSAAD
article en

Abstract

Insulating a heritage masonry wall from the inside is often the only option when the façade must be preserved — and it is also the most likely to fail, because it traps moisture where the insulation meets the wall. Which bio-based systems survive this, and on which façades, is still poorly understood in oceanic climates. To find out, four bio-based systems — hemp–lime concrete, cellulose wadding, sheep wool and flax wool — were installed on the four differently oriented façades of a historic brick building in northern France and monitored for a year at the insulation–masonry interface, and mould risk was assessed with the extended VTT model. The three fibrous walls had near-identical U-values (0.099–0.107 W·m⁻²·K⁻¹) and thermal masses (567–575 kJ·m⁻²·K⁻¹), and almost identical interface vapour pressures. Differences in their mould response can therefore be attributed mainly to orientation rather than to the insulation material. Their mould indices ranged from below 1 to above 3: colder north-facing interfaces held the relative humidity high enough for mould, while sunnier façades stayed dry. The north-west flax-wool wall spent 256 days above 90% relative humidity and reached a mould index above 3; the south-east hemp–lime wall averaged 69% and stayed below 0.3. This failing wall was reproduced in a calibrated heat-and-moisture model and six corrective measures were tested over three simulated years. The most effective was counter-intuitive: removing the smart vapour retarder — a layer meant to control moisture — was the only measure that brought the mould index back to zero. Thinner insulation helped by warming the interface, while a vapour barrier, thicker insulation, or a hemp–lime replacement all made things worse. The result is orientation-specific guidance for using bio-based internal insulation safely in oceanic climates.

Case Studies in Construction MaterialsVol. 25
Université de Lille (FR), JUNIA (FR), IMT Nord Europe (FR), Laboratoire de Génie Civil et Géo Environnement (FR), Université d'Artois (FR)
Responsible consumption and production
Openalex Percentile: Top 16%
Hygrothermal properties of building materials
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon