Impact of Reactive Power Fluctuation on the Performance and Insulation Loss-of-Life Rate of Industrial Power Transformers: A Case Study of the PT Semen Tonasa Electrical System

Power transformer performance is strongly influenced by reactive power (VAR), yet the quantitative link between VAR fluctuation and insulation loss-of-life in heavy industrial systems remains under-documented. This study analyzes that link for six 70 kV power transformers (three at the Tonasa IV and three at the Tonasa V substations, 31.5–40 MVA) in the electrical system of PT Semen Tonasa, combining SCADA operational data, an ETAP load-flow simulation, and an analytical ageing-rate calculation based on IEC 60076-7. Varying reactive power from 1 to 10 MVAR at a fixed active power of 10 MW increased the loading level from 31.41% to 44.19% of the 80% operating limit, consistent with S = √(P²+Q²). SCADA records showed current rising and primary-side voltage falling as VAR increased, with all voltages (66.68–68.95 kV) remaining within ±10% of nominal. For the three Tonasa V units, hotspot temperatures of 65.42–75.23°C and loss-of-life rates of 0.022–0.069 pu/day were obtained, well below the 98°C/V = 1 design reference; Transformer #1 aged roughly 3.1 times faster than Transformer #2, reflecting its higher average loading (63.4% vs. 36.5% of the operating limit). The extrapolated remaining-life figures (79.7–250 years) are indicative rather than literal, given the short (3–5-day) SCADA window; the loss-of-life rate is therefore treated as the primary, more defensible indicator. Reactive-power compensation via capacitor banks or static var compensators is recommended to limit current, hotspot temperature, and insulation ageing.

Authors

Institutions

Publication Details

Journal
PROtek Jurnal Ilmiah Teknik Elektro
Published
2026-10-28
DOI
https://doi.org/10.33387/protk.v13i2.12746
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Impact of Reactive Power Fluctuation on the Performance and Insulation Loss-of-Life Rate of Industrial Power Transformers: A Case Study of the PT Semen Tonasa Electrical System

Muh. Imran Bachtiar, Rahmat Budiansa, Aksan
2 links
PROtek Jurnal Ilmiah Teknik Elektro
Power Transformer Diagnostics and Insulation
article

Impact of Reactive Power Fluctuation on the Performance and Insulation Loss-of-Life Rate of Industrial Power Transformers: A Case Study of the PT Semen Tonasa Electrical System

Muh. Imran Bachtiar, Rahmat Budiansa, Aksan
article en

Abstract

Power transformer performance is strongly influenced by reactive power (VAR), yet the quantitative link between VAR fluctuation and insulation loss-of-life in heavy industrial systems remains under-documented. This study analyzes that link for six 70 kV power transformers (three at the Tonasa IV and three at the Tonasa V substations, 31.5–40 MVA) in the electrical system of PT Semen Tonasa, combining SCADA operational data, an ETAP load-flow simulation, and an analytical ageing-rate calculation based on IEC 60076-7. Varying reactive power from 1 to 10 MVAR at a fixed active power of 10 MW increased the loading level from 31.41% to 44.19% of the 80% operating limit, consistent with S = √(P²+Q²). SCADA records showed current rising and primary-side voltage falling as VAR increased, with all voltages (66.68–68.95 kV) remaining within ±10% of nominal. For the three Tonasa V units, hotspot temperatures of 65.42–75.23°C and loss-of-life rates of 0.022–0.069 pu/day were obtained, well below the 98°C/V = 1 design reference; Transformer #1 aged roughly 3.1 times faster than Transformer #2, reflecting its higher average loading (63.4% vs. 36.5% of the operating limit). The extrapolated remaining-life figures (79.7–250 years) are indicative rather than literal, given the short (3–5-day) SCADA window; the loss-of-life rate is therefore treated as the primary, more defensible indicator. Reactive-power compensation via capacitor banks or static var compensators is recommended to limit current, hotspot temperature, and insulation ageing.

PROtek Jurnal Ilmiah Teknik ElektroVol. 13(2)
Politeknik Negeri Ujung Pandang (ID)
Politeknik Negeri Ujung Pandang
Industry, innovation and infrastructure, Affordable and clean energy
Openalex Percentile: Top 24%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon