Integrating parametric design, field-evaluated hygrothermal simulation and life-cycle assessment for early-stage low-carbon envelope decisions: a pilot demonstration on a full-scale salt-brick pavilion in a hot-arid climate

Purpose This study pilot-demonstrates the Climate-Adaptive Mineral Envelope (CAME) workflow, integrating fragmented analytical tools within Grasshopper to support low-carbon envelope decisions for hot-arid construction.Design/methodology/approach A discretised Schwarz P envelope underwent structural verification and NSGA-II optimisation using a Gaussian-process surrogate trained on 120 EnergyPlus simulations. A Pareto-knee configuration was built as a 3,000-brick Himalayan salt pavilion exhibited at Dubai Design Week 2024. Nine-day monitoring of operative and surface temperatures and relative humidity informed calibration of an EnergyPlus model using the Effective Moisture Penetration Depth algorithm. Screening life-cycle assessment (LCA) and costing completed the work flow.Findings Surrogate RMSE was 0.38 °C under leave-one-out cross-validation and 0.42 °C across six out-of-sample simulations. Calibrated model RMSE was 1.06–1.31 °C, with CV(RMSE) of 3.4–3.6%. NMBE was not calculated, precluding full ASHRAE Guideline 14 compliance claims. Mean operative temperature in the salt cavity was 3.1 °C below the concrete-masonry-unit reference, with a 6.3-h phase shift and 0.43 decrement factor. These contrasts are descriptive because observations were serially correlated, monitoring covered one pavilion and one panel, and cavity-node convective exposure was unquantified. Screening LCA indicated 69.7% lower embodied carbon, remaining ≥62.3% across a ±50% sensitivity band.Originality/value The workflow connects parametric design, surrogate-assisted optimisation, fabrication, monitoring and calibrated simulation with carbon and cost screening, assigning explicit evidence-status classifications.Practical implications Comparative thermal, carbon and cost screening is delivered within one working session. Permanent salt-envelope application requires binder redesign, deliquescence-resistant detailing and code-compliance evidence.

Authors

Institutions

Publication Details

Journal
Architectural Engineering and Design Management
Published
2026-10-17
DOI
https://doi.org/10.1080/17452007.2026.2747380
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Integrating parametric design, field-evaluated hygrothermal simulation and life-cycle assessment for early-stage low-carbon envelope decisions: a pilot demonstration on a full-scale salt-brick pavilion in a hot-arid climate

Aseel Ali Hussien, Aref Mohamad Maksoud, Shouib Nouh Ma’bdeh
Architectural Engineering and Design Management
Building Energy and Comfort Optimization
article

Integrating parametric design, field-evaluated hygrothermal simulation and life-cycle assessment for early-stage low-carbon envelope decisions: a pilot demonstration on a full-scale salt-brick pavilion in a hot-arid climate

Aseel Ali Hussien, Aref Mohamad Maksoud, Shouib Nouh Ma’bdeh
article en

Abstract

Purpose This study pilot-demonstrates the Climate-Adaptive Mineral Envelope (CAME) workflow, integrating fragmented analytical tools within Grasshopper to support low-carbon envelope decisions for hot-arid construction.Design/methodology/approach A discretised Schwarz P envelope underwent structural verification and NSGA-II optimisation using a Gaussian-process surrogate trained on 120 EnergyPlus simulations. A Pareto-knee configuration was built as a 3,000-brick Himalayan salt pavilion exhibited at Dubai Design Week 2024. Nine-day monitoring of operative and surface temperatures and relative humidity informed calibration of an EnergyPlus model using the Effective Moisture Penetration Depth algorithm. Screening life-cycle assessment (LCA) and costing completed the work flow.Findings Surrogate RMSE was 0.38 °C under leave-one-out cross-validation and 0.42 °C across six out-of-sample simulations. Calibrated model RMSE was 1.06–1.31 °C, with CV(RMSE) of 3.4–3.6%. NMBE was not calculated, precluding full ASHRAE Guideline 14 compliance claims. Mean operative temperature in the salt cavity was 3.1 °C below the concrete-masonry-unit reference, with a 6.3-h phase shift and 0.43 decrement factor. These contrasts are descriptive because observations were serially correlated, monitoring covered one pavilion and one panel, and cavity-node convective exposure was unquantified. Screening LCA indicated 69.7% lower embodied carbon, remaining ≥62.3% across a ±50% sensitivity band.Originality/value The workflow connects parametric design, surrogate-assisted optimisation, fabrication, monitoring and calibrated simulation with carbon and cost screening, assigning explicit evidence-status classifications.Practical implications Comparative thermal, carbon and cost screening is delivered within one working session. Permanent salt-envelope application requires binder redesign, deliquescence-resistant detailing and code-compliance evidence.

Architectural Engineering and Design Management
University of Sharjah (AE)
Climate action, Sustainable cities and communities, Responsible consumption and production, Affordable and clean energy, Industry, innovation and infrastructure
Openalex Percentile: Top 16%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.