Logistic model-based study on fouling thermal resistance evolution and anti-fouling strategies for bathing wastewater-source heat pump heat exchangers

Bathing wastewater-source heat pumps can recover low-grade waste heat, but complex contaminants may cause heat-exchanger fouling and deteriorate heat-transfer performance. This study investigated fouling evolution and control strategies for an immersed copper-tube heat exchanger using physical filtration and composite chemical treatment. Fouling thermal resistance was evaluated using the thermal-resistance difference method and fitted using the Kern–Seaton (KS) and Logistic models. During a 72 h test with untreated wastewater, the overall heat-transfer coefficient decreased by 28.21%, while the overall thermal resistance increased by 39.4%. Baseline filtration at 0.52 mm reduced the steady-state overall thermal resistance by 18.08%, whereas further filtration to 0.25 and 0.04 mm provided limited additional improvement. The Logistic model better described the observed fouling evolution than the KS model, with R 2 increasing from 0.953 to 0.976 and RMSE decreasing by 28.4%. The fitted asymptotic fouling thermal resistance decreased from 5.56 × 10 −4 m 2 ·K/W without filtration to 2.13 × 10 −4 , 1.85 × 10 −4 , and 1.15 × 10 −4 m 2 ·K/W at filtration cut-offs of 0.52, 0.25, and 0.04 mm, respectively. Water-quality indicators suggested a low CaCO₃ scaling tendency and substantial microbial activity in the bulk water; however, these indirect indicators did not establish the dominant fouling mechanism. Orthogonal screening identified a formulation containing 8 mg/L ATMP, 10 mg/L PAA, 30 mg/L GLDA, 30 mg/L TDBAC, and 5 mg/L BTA. Combined with 0.52 mm filtration, this treatment maintained stable heat-transfer performance during a 72 h verification test. These results demonstrate the potential of combining baseline filtration with chemical treatment for fouling control in bathing wastewater heat exchangers.

Authors

Institutions

Publication Details

Journal
International Communications in Heat and Mass Transfer
Published
2026-10-15
DOI
https://doi.org/10.1016/j.icheatmasstransfer.2026.112875
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Logistic model-based study on fouling thermal resistance evolution and anti-fouling strategies for bathing wastewater-source heat pump heat exchangers

Erlin Meng, Haiqian Zhao, Xianxin Ge, Mengling Dai et al.
International Communications in Heat and Mass Transfer
Heat Transfer and Optimization
article

Logistic model-based study on fouling thermal resistance evolution and anti-fouling strategies for bathing wastewater-source heat pump heat exchangers

Erlin Meng, Haiqian Zhao, Xianxin Ge, Mengling Dai, Jun Li
article en

Abstract

Bathing wastewater-source heat pumps can recover low-grade waste heat, but complex contaminants may cause heat-exchanger fouling and deteriorate heat-transfer performance. This study investigated fouling evolution and control strategies for an immersed copper-tube heat exchanger using physical filtration and composite chemical treatment. Fouling thermal resistance was evaluated using the thermal-resistance difference method and fitted using the Kern–Seaton (KS) and Logistic models. During a 72 h test with untreated wastewater, the overall heat-transfer coefficient decreased by 28.21%, while the overall thermal resistance increased by 39.4%. Baseline filtration at 0.52 mm reduced the steady-state overall thermal resistance by 18.08%, whereas further filtration to 0.25 and 0.04 mm provided limited additional improvement. The Logistic model better described the observed fouling evolution than the KS model, with R 2 increasing from 0.953 to 0.976 and RMSE decreasing by 28.4%. The fitted asymptotic fouling thermal resistance decreased from 5.56 × 10 −4 m 2 ·K/W without filtration to 2.13 × 10 −4 , 1.85 × 10 −4 , and 1.15 × 10 −4 m 2 ·K/W at filtration cut-offs of 0.52, 0.25, and 0.04 mm, respectively. Water-quality indicators suggested a low CaCO₃ scaling tendency and substantial microbial activity in the bulk water; however, these indirect indicators did not establish the dominant fouling mechanism. Orthogonal screening identified a formulation containing 8 mg/L ATMP, 10 mg/L PAA, 30 mg/L GLDA, 30 mg/L TDBAC, and 5 mg/L BTA. Combined with 0.52 mm filtration, this treatment maintained stable heat-transfer performance during a 72 h verification test. These results demonstrate the potential of combining baseline filtration with chemical treatment for fouling control in bathing wastewater heat exchangers.

International Communications in Heat and Mass TransferVol. 180
Suzhou University of Science and Technology (CN), Tianping College of Suzhou University of Science and Technology (CN)
Clean water and sanitation
Openalex Percentile: Top 23%
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.