PV-ESS Integrated Operation Analysis of a Major Railway Station Based on Measured Load: 15-min Peak Demand and Time-of-Use Tariff

Railway stations run continuously with flat, base-load-dominated electricity demand, so the value of photovoltaics (PV) and energy storage (ESS) differs from buildings with daily peaks. This study analyzes PV-ESS integrated operation for SRT station using twelve months of metered hourly electricity and within-hour 15-minute maximum demand, the 202 kW rooftop PV scaled to its 2024 measured yield, and the industrial time-of-use (TOU) tariff with weekend and holiday rules. The load averages 685 kW with a load factor of 0.55 and an annual 15-minute peak of 1,245 kW as short spikes; PV covers 4.1% of demand with no export. Expanding rooftop PV to about 1,000 kW keeps self-consumption at 100% but raises self-sufficiency only to 20% and cuts the annual peak by only 38 kW. For flat-load stations the value of storage lies in demand-charge reduction rather than arbitrage or self-sufficiency.

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2026-10-15
DOI
https://doi.org/10.5370/kiee.2026.75.10.2721
Primary Topic
Smart Grid Energy Management
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

PV-ESS Integrated Operation Analysis of a Major Railway Station Based on Measured Load: 15-min Peak Demand and Time-of-Use Tariff

Seung-Kwon Shin
The Transactions of The Korean Institute of Electrical Engineers
Smart Grid Energy Management
article

PV-ESS Integrated Operation Analysis of a Major Railway Station Based on Measured Load: 15-min Peak Demand and Time-of-Use Tariff

Seung-Kwon Shin
article en

Abstract

Railway stations run continuously with flat, base-load-dominated electricity demand, so the value of photovoltaics (PV) and energy storage (ESS) differs from buildings with daily peaks. This study analyzes PV-ESS integrated operation for SRT station using twelve months of metered hourly electricity and within-hour 15-minute maximum demand, the 202 kW rooftop PV scaled to its 2024 measured yield, and the industrial time-of-use (TOU) tariff with weekend and holiday rules. The load averages 685 kW with a load factor of 0.55 and an annual 15-minute peak of 1,245 kW as short spikes; PV covers 4.1% of demand with no export. Expanding rooftop PV to about 1,000 kW keeps self-consumption at 100% but raises self-sufficiency only to 20% and cuts the annual peak by only 38 kW. For flat-load stations the value of storage lies in demand-charge reduction rather than arbitrage or self-sufficiency.

The Transactions of The Korean Institute of Electrical EngineersVol. 75(10)
Affordable and clean energy, Industry, innovation and infrastructure, Climate action, Sustainable cities and communities
Openalex Percentile: Top 24%
Smart Grid Energy Management
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.