Analysis of Electric Field Redistribution in Oil-Pressboard Insulation of a ±525 kV HVDC Converter Transformer under AC/DC Superimposed Voltage

HVDC converter transformers are subjected to complex electrical stresses because AC and DC voltage components coexist on the valve winding. This study investigates time-dependent electric-field redistribution in the oil-pressboard insulation of a ±525 kV VSC-HVDC converter transformer under an earth-referenced AC/DC superimposed valve-winding voltage obtained from system-level steady-state analysis. A time-dependent finite-element electric-field analysis was performed in COMSOL Multiphysics using fixed electrical properties of insulating oil and pressboard. The electric field was initially concentrated in the oil channels but gradually shifted toward the pressboard barriers due to Maxwell-Wagner field redistribution. The Maxwell-Wagner relaxation times for the different barrier configurations ranged from approximately 3.49 to 5.79 s, and the 50 s analysis period covered a period in which the field variation became gradual following the major redistribution. With the inter-barrier oil-gap thickness fixed at 2 mm and the total insulation distance maintained at 110 mm, the pressboard barrier thickness and number were varied, thereby changing the overall pressboard fraction. At 50 s, the maximum pressboard electric field decreased from 16.9 to 10.8 kV/mm, corresponding to a reduction of approximately 36%, while the oil-channel electric field remained within a relatively similar range despite changes in the overall insulation configuration. These results highlight the need to consider time-dependent electric-field redistribution caused by the sustained DC component of AC/DC superimposed voltage in HVDC converter-transformer insulation design.

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2026-10-15
DOI
https://doi.org/10.5370/kiee.2026.75.10.2513
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of Electric Field Redistribution in Oil-Pressboard Insulation of a ±525 kV HVDC Converter Transformer under AC/DC Superimposed Voltage

Chan-Yeol Ryu, Sang-Hoon Park, Chandra Sekhar Reddy, Geon Go et al.
The Transactions of The Korean Institute of Electrical Engineers
High voltage insulation and dielectric phenomena
article

Analysis of Electric Field Redistribution in Oil-Pressboard Insulation of a ±525 kV HVDC Converter Transformer under AC/DC Superimposed Voltage

Chan-Yeol Ryu, Sang-Hoon Park, Chandra Sekhar Reddy, Geon Go, Bang-Wook Lee
article en

Abstract

HVDC converter transformers are subjected to complex electrical stresses because AC and DC voltage components coexist on the valve winding. This study investigates time-dependent electric-field redistribution in the oil-pressboard insulation of a ±525 kV VSC-HVDC converter transformer under an earth-referenced AC/DC superimposed valve-winding voltage obtained from system-level steady-state analysis. A time-dependent finite-element electric-field analysis was performed in COMSOL Multiphysics using fixed electrical properties of insulating oil and pressboard. The electric field was initially concentrated in the oil channels but gradually shifted toward the pressboard barriers due to Maxwell-Wagner field redistribution. The Maxwell-Wagner relaxation times for the different barrier configurations ranged from approximately 3.49 to 5.79 s, and the 50 s analysis period covered a period in which the field variation became gradual following the major redistribution. With the inter-barrier oil-gap thickness fixed at 2 mm and the total insulation distance maintained at 110 mm, the pressboard barrier thickness and number were varied, thereby changing the overall pressboard fraction. At 50 s, the maximum pressboard electric field decreased from 16.9 to 10.8 kV/mm, corresponding to a reduction of approximately 36%, while the oil-channel electric field remained within a relatively similar range despite changes in the overall insulation configuration. These results highlight the need to consider time-dependent electric-field redistribution caused by the sustained DC component of AC/DC superimposed voltage in HVDC converter-transformer insulation design.

The Transactions of The Korean Institute of Electrical EngineersVol. 75(10)
Affordable and clean energy
Openalex Percentile: Top 28%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.