Evaluation of Flashover Voltage and Proposal of Management Criteria Based on Critical Pollution Level for Indoor Switchgear Post Insulators

Indoor switchgear is generally considered low-risk for pollution; however, dust and salt can accumulate on insulator surfaces during long-term operation, raising flashover risk under humid conditions. This study evaluated soluble and non-soluble pollution effects on 12 kV-class epoxy post insulators under Type A pollution. Soluble pollution was varied through the equivalent salt deposit density (ESDD), and non-soluble pollution through the kaolin content and resulting non-soluble deposit density (NSDD). Relative to the clean condition, flashover voltage decreased by about 30% and 44% at ESDD levels of 0.05 and 0.1 mg/cm², respectively; these are proposed as critical pollution levels for the action and urgent management criteria. Using environment-specific accumulation rates for five service scenarios, the urgent criterion was reached after about 120 months in clean environments but only 3.2 months in coastal and offshore environments, supporting differentiated maintenance intervals.

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2026-10-15
DOI
https://doi.org/10.5370/kiee.2026.75.10.2504
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluation of Flashover Voltage and Proposal of Management Criteria Based on Critical Pollution Level for Indoor Switchgear Post Insulators

Bonhyuk Ku, Hyoungku Kang, Inhoo Ban, Chanhyeok Jang et al.
The Transactions of The Korean Institute of Electrical Engineers
High voltage insulation and dielectric phenomena
article

Evaluation of Flashover Voltage and Proposal of Management Criteria Based on Critical Pollution Level for Indoor Switchgear Post Insulators

Bonhyuk Ku, Hyoungku Kang, Inhoo Ban, Chanhyeok Jang, Giwon Go, Jehui Lee, Yechan Kim
article en

Abstract

Indoor switchgear is generally considered low-risk for pollution; however, dust and salt can accumulate on insulator surfaces during long-term operation, raising flashover risk under humid conditions. This study evaluated soluble and non-soluble pollution effects on 12 kV-class epoxy post insulators under Type A pollution. Soluble pollution was varied through the equivalent salt deposit density (ESDD), and non-soluble pollution through the kaolin content and resulting non-soluble deposit density (NSDD). Relative to the clean condition, flashover voltage decreased by about 30% and 44% at ESDD levels of 0.05 and 0.1 mg/cm², respectively; these are proposed as critical pollution levels for the action and urgent management criteria. Using environment-specific accumulation rates for five service scenarios, the urgent criterion was reached after about 120 months in clean environments but only 3.2 months in coastal and offshore environments, supporting differentiated maintenance intervals.

The Transactions of The Korean Institute of Electrical EngineersVol. 75(10)
Industry, innovation and infrastructure
Openalex Percentile: Top 29%
High voltage insulation and dielectric phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.