An experimental investigation of flow boiling heat transfer characteristics and the triggering mechanisms of CHF in a natural circulation loop under moderate to low driving forces

Flow boiling heat transfer, flow instability, and critical heat flux (CHF) were investigated experimentally in a vertical R134a natural circulation loop with an integrated reservoir. Tests on flow heat transfer characteristics and flow visualization were conducted at filling ratios of 25–85% and cooling water temperatures of 10–22 °C. Higher peak heat transfer coefficients were obtained in the filling ratio range of 25–45%, with a maximum measured value of 16,145.5 W·m −2 ·K −1 . At a cooling water temperature of 14 °C, regular pressure and temperature oscillations were first detected at heat fluxes of 49.10–71.71 kW·m −2 , with frequencies of 0.453–0.628 Hz. The measured CHF increased by approximately 50% across filling ratios of 25–75%, rising from about 100–150 kW·m −2 . At a 75% filling ratio, the CHF increased from approximately 132–151 kW·m −2 as the cooling water temperature rose from 10 to 14 °C, with no further increase observed up to 22 °C. The CHF was not determined at an 85% filling ratio due to equipment pressure constraints. The onset of sustained wall-temperature excursion was distinguished from subsequent post-CHF heat transfer deterioration. Flow-pattern observations and circulation measurements suggested that insufficient liquid supply relative to evaporation induced the occurrence of CHF. The Benkheira correlation predicted all CHF measurements within the range of −22.72% to + 23.31%, providing an approximate estimation for the present dataset. As indicated by the above-mentioned results, the conditions yielding higher heat transfer coefficients differed from those maintaining higher limiting heat loads.

Authors

Institutions

Publication Details

Journal
International Journal of Heat and Mass Transfer
Published
2026-10-15
DOI
https://doi.org/10.1016/j.ijheatmasstransfer.2026.129749
Primary Topic
Heat Transfer and Boiling Studies
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An experimental investigation of flow boiling heat transfer characteristics and the triggering mechanisms of CHF in a natural circulation loop under moderate to low driving forces

Yuhao Zhang, Song Feng, Linsen Mu, Liankai Zhao et al.
International Journal of Heat and Mass Transfer
Heat Transfer and Boiling Studies
article

An experimental investigation of flow boiling heat transfer characteristics and the triggering mechanisms of CHF in a natural circulation loop under moderate to low driving forces

Yuhao Zhang, Song Feng, Linsen Mu, Liankai Zhao, Teng Wang, Lu Liu
article en

Abstract

Flow boiling heat transfer, flow instability, and critical heat flux (CHF) were investigated experimentally in a vertical R134a natural circulation loop with an integrated reservoir. Tests on flow heat transfer characteristics and flow visualization were conducted at filling ratios of 25–85% and cooling water temperatures of 10–22 °C. Higher peak heat transfer coefficients were obtained in the filling ratio range of 25–45%, with a maximum measured value of 16,145.5 W·m −2 ·K −1 . At a cooling water temperature of 14 °C, regular pressure and temperature oscillations were first detected at heat fluxes of 49.10–71.71 kW·m −2 , with frequencies of 0.453–0.628 Hz. The measured CHF increased by approximately 50% across filling ratios of 25–75%, rising from about 100–150 kW·m −2 . At a 75% filling ratio, the CHF increased from approximately 132–151 kW·m −2 as the cooling water temperature rose from 10 to 14 °C, with no further increase observed up to 22 °C. The CHF was not determined at an 85% filling ratio due to equipment pressure constraints. The onset of sustained wall-temperature excursion was distinguished from subsequent post-CHF heat transfer deterioration. Flow-pattern observations and circulation measurements suggested that insufficient liquid supply relative to evaporation induced the occurrence of CHF. The Benkheira correlation predicted all CHF measurements within the range of −22.72% to + 23.31%, providing an approximate estimation for the present dataset. As indicated by the above-mentioned results, the conditions yielding higher heat transfer coefficients differed from those maintaining higher limiting heat loads.

International Journal of Heat and Mass TransferVol. 273
North China Electric Power University (CN), China Aerodynamics Research and Development Center (CN)
National Natural Science Foundation of China, Natural Science Foundation of Hebei Province, National University's Basic Research Foundation of China
Openalex Percentile: Top 23%
Heat Transfer and Boiling Studies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.