Local Faulted-Section Identification for Pole-to-Pole Faults in MVDC Ring Networks Using Hybrid DC Circuit-Breaker Commutation Characteristics

Fast and selective faulted-section identification is challenging in multiterminal medium-voltage DC (MVDC) ring networks because the initial fault transient is affected by converter dynamics, fault resistance, line parameters, and multiple feeding paths. This paper proposes a local identification method for pole-to-pole faults in a four-terminal ±10 kV modular multilevel converter (MMC)-based MVDC ring network, using hybrid DC circuit-breaker (HCB) commutation characteristics. The breaker-current magnitude is used to initiate hybrid DC circuit breaker operation. The identification feature is the magnitude of the mechanical-switch (MS) current slope estimated during the passive intervals of the clamped commutation stage. This feature is used to classify faults as in-zone or out-of-zone. An in-zone fault is confirmed when three consecutive valid slope estimates satisfy the threshold criterion. Because only local HCB measurements and control signals are required for online identification, the method does not rely on interterminal communication or time synchronization. Offline threshold setting, however, requires the network topology and component parameters. After classification, the HCBs bounding the faulted line continue the interruption process, whereas triggered out-of-zone HCBs maintain semiconductor conduction and subsequently reclose their MSs. PSCAD/EMTDC simulations on a four-terminal ±10 kV MVDC ring network demonstrate correct faulted-section identification at the end of a 200 μs decision interval measured from local HCB triggering, using a baseline protection sampling interval of 1 μs, over the tested fault locations and fault resistance. Additional sampling-interval tests show no observed identification failures at 1 and 2 μs for the evaluated cases, whereas failures occur at 5 μs. Additional bounded measurement-noise tests show correct discrimination for the benchmark fault at the tested nominal noise levels up to 1% for the selected noise realizations. These results demonstrate the feasibility for the studied configuration; broader parameter variations and practical measurement and execution constraints require further validation.

Authors

Institutions

Publication Details

Journal
Machines
Published
2026-10-14
DOI
https://doi.org/10.3390/machines14101188
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Local Faulted-Section Identification for Pole-to-Pole Faults in MVDC Ring Networks Using Hybrid DC Circuit-Breaker Commutation Characteristics

Cong Zhu, Risha Na, Jun Tao, Tingwei Liang et al.
Machines
HVDC Systems and Fault Protection
article

Local Faulted-Section Identification for Pole-to-Pole Faults in MVDC Ring Networks Using Hybrid DC Circuit-Breaker Commutation Characteristics

Cong Zhu, Risha Na, Jun Tao, Tingwei Liang, Haitao Yan, Zhengyi Sun, Xin Wang, Chi Zhang
article en

Abstract

Fast and selective faulted-section identification is challenging in multiterminal medium-voltage DC (MVDC) ring networks because the initial fault transient is affected by converter dynamics, fault resistance, line parameters, and multiple feeding paths. This paper proposes a local identification method for pole-to-pole faults in a four-terminal ±10 kV modular multilevel converter (MMC)-based MVDC ring network, using hybrid DC circuit-breaker (HCB) commutation characteristics. The breaker-current magnitude is used to initiate hybrid DC circuit breaker operation. The identification feature is the magnitude of the mechanical-switch (MS) current slope estimated during the passive intervals of the clamped commutation stage. This feature is used to classify faults as in-zone or out-of-zone. An in-zone fault is confirmed when three consecutive valid slope estimates satisfy the threshold criterion. Because only local HCB measurements and control signals are required for online identification, the method does not rely on interterminal communication or time synchronization. Offline threshold setting, however, requires the network topology and component parameters. After classification, the HCBs bounding the faulted line continue the interruption process, whereas triggered out-of-zone HCBs maintain semiconductor conduction and subsequently reclose their MSs. PSCAD/EMTDC simulations on a four-terminal ±10 kV MVDC ring network demonstrate correct faulted-section identification at the end of a 200 μs decision interval measured from local HCB triggering, using a baseline protection sampling interval of 1 μs, over the tested fault locations and fault resistance. Additional sampling-interval tests show no observed identification failures at 1 and 2 μs for the evaluated cases, whereas failures occur at 5 μs. Additional bounded measurement-noise tests show correct discrimination for the benchmark fault at the tested nominal noise levels up to 1% for the selected noise realizations. These results demonstrate the feasibility for the studied configuration; broader parameter variations and practical measurement and execution constraints require further validation.

MachinesVol. 14(10)
Anhui University (CN)
Industry, innovation and infrastructure
Openalex Percentile: Top 24%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.