Energy and thermal comfort assessment of insulation strategies in Moroccan residential buildings: a multi-zone simulation study based on the Moroccan thermal construction regulation

Abstract Thermal insulation is the main lever for cutting building energy demand in Morocco, yet no unified comparison of insulation materials exists across the six climatic zones of the Moroccan Thermal Construction Regulation. One two-storey dwelling of 100.05 m² was simulated in all six zones with DesignBuilder and EnergyPlus: 562 runs covering six conventional insulation materials at five thicknesses, three envelope configurations, and one phase-change material treated separately. Heating and cooling are reported as ideal sensible loads. The conduction and surface heat-balance formulation is first verified against published cavity measurements from Errachidia, reproducing the measured outer surface temperature with a root mean square error of 0.41 K during charging and 0.95 K over a 22-hour cycle, without parameter fitting. Extruded polystyrene applied to walls and roof at 6/6 cm gives the largest reduction in annual demand in every zone, from 12.55% in Agadir to 27.19% in Ifrane. Compared at equal thermal resistance rather than equal thickness, however, the six materials agree to within 0.05 percentage points: the advantage of polymer foams reflects only the thickness needed to reach a given resistance, 4.63 cm of XPS against 6.63 cm of wood fiber. Lowest demand does not coincide with best comfort. Wall insulation raises discomfort hours in every scenario tested in Agadir and Errachidia, because it suppresses the opaque envelope, the dwelling's dominant heat sink, removing 19199 kWh yearly in the reference case; roof insulation degrades comfort nowhere. Insulation should be selected by climatic zone and envelope component, not by conductivity alone.

Authors

Institutions

Publication Details

Journal
Journal of Building Pathology and Rehabilitation
Published
2026-11-16
DOI
https://doi.org/10.1007/s41024-026-00930-7
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

Energy and thermal comfort assessment of insulation strategies in Moroccan residential buildings: a multi-zone simulation study based on the Moroccan thermal construction regulation

My Chrif Elboubakraoui, Hicham Kaddouri, A. BOUCHARK, Abdelmajid El Bakkali
Journal of Building Pathology and Rehabilitation
Building Energy and Comfort Optimization
article

Energy and thermal comfort assessment of insulation strategies in Moroccan residential buildings: a multi-zone simulation study based on the Moroccan thermal construction regulation

My Chrif Elboubakraoui, Hicham Kaddouri, A. BOUCHARK, Abdelmajid El Bakkali
article en

Abstract

Abstract Thermal insulation is the main lever for cutting building energy demand in Morocco, yet no unified comparison of insulation materials exists across the six climatic zones of the Moroccan Thermal Construction Regulation. One two-storey dwelling of 100.05 m² was simulated in all six zones with DesignBuilder and EnergyPlus: 562 runs covering six conventional insulation materials at five thicknesses, three envelope configurations, and one phase-change material treated separately. Heating and cooling are reported as ideal sensible loads. The conduction and surface heat-balance formulation is first verified against published cavity measurements from Errachidia, reproducing the measured outer surface temperature with a root mean square error of 0.41 K during charging and 0.95 K over a 22-hour cycle, without parameter fitting. Extruded polystyrene applied to walls and roof at 6/6 cm gives the largest reduction in annual demand in every zone, from 12.55% in Agadir to 27.19% in Ifrane. Compared at equal thermal resistance rather than equal thickness, however, the six materials agree to within 0.05 percentage points: the advantage of polymer foams reflects only the thickness needed to reach a given resistance, 4.63 cm of XPS against 6.63 cm of wood fiber. Lowest demand does not coincide with best comfort. Wall insulation raises discomfort hours in every scenario tested in Agadir and Errachidia, because it suppresses the opaque envelope, the dwelling's dominant heat sink, removing 19199 kWh yearly in the reference case; roof insulation degrades comfort nowhere. Insulation should be selected by climatic zone and envelope component, not by conductivity alone.

Journal of Building Pathology and RehabilitationVol. 12(1)
Abdelmalek Essaâdi University (MA), Université Moulay Ismail de Meknes (MA)
Climate action, Sustainable cities and communities, Affordable and clean energy
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon