Development of a functional and disinfectable sewage vent high-efficiency particulate air filter system and its validation using vaporized hydrogen peroxide

ABSTRACT Airborne disinfection of high-containment facilities is mandatory for safe operations. However, sewage vent air—particularly in large-animal experimental units—can represent a critical gap and is typically not considered in the design of high-efficiency particulate air (HEPA) filter systems. Here, we present an engineering design enabling HEPA filtration of sewage vent air from primary biological containments, including large-animal facilities and necropsy suites. We additionally evaluated vaporized hydrogen peroxide (vH 2 O 2 ) fumigation as an airborne disinfection approach. Disinfection efficacy was determined by quantitative carrier testing using commercial spore carriers (CSC) coated with 10 6 spores of Geobacillus stearothermophilus and compared with germ carriers coated with surrogate viruses, mycobacteria, and other spores. Temperature, relative humidity (RH), and vH 2 O 2 concentration were monitored in real time to define process parameters and validate protocols targeting ≥4 log 10 reduction. Inactivation efficacy differed substantially among challenge agents: CSC were least resistant to inactivation, whereas murine norovirus (MNV) on germ carriers was most challenging to inactivate. At medium-high vH 2 O 2 concentrations (up to 520 parts per million [ppm]), increasing RH was the dominant driver of inactivation. Based on these data, we developed a biphasic disinfection cycle maintaining a saturated humidity environment with ~35% H 2 O 2 for ≥10 h, achieving ≥4 log 10 reduction of MNV infectivity and G. stearothermophilus spore viability on germ carriers. Overall, vH 2 O 2 under high-to-saturated RH is an effective means to disinfect technical infrastructure in biological containment settings handling high-consequence pathogens. IMPORTANCE Vent air from sewage systems in biological containment facilities where large animals are kept should be considered a contaminated waste stream. Therefore, effective high-efficiency particulate air (HEPA) filter systems that prevent mold or other moisture-related deterioration of the filters need to be installed. Airborne vaporized hydrogen peroxide (vH 2 O 2 ) is an appropriate method to decontaminate these complex HEPA filter systems. High to saturated humidity is required for virucidal and sporicidal efficacy under medium to high concentration of vH 2 O 2 . Commercially available spore carriers are artificial in design, resulting in lower resistance to inactivation compared to custom germ carriers coated with non-enveloped viruses and thus should be avoided as read-out (validation means) by the biosafety community working with high-consequence pathogens in primary containments.

Authors

Institutions

Publication Details

Journal
Applied and Environmental Microbiology
Published
2026-09-09
DOI
https://doi.org/10.1128/aem.01269-26
Primary Topic
Viral gastroenteritis research and epidemiology
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Development of a functional and disinfectable sewage vent high-efficiency particulate air filter system and its validation using vaporized hydrogen peroxide

Hendrik Scheinemann, Michael Eschbaumer, Sven Reiche, Holger Freese et al.
Applied and Environmental Microbiology
Viral gastroenteritis research and epidemiology
article

Development of a functional and disinfectable sewage vent high-efficiency particulate air filter system and its validation using vaporized hydrogen peroxide

Hendrik Scheinemann, Michael Eschbaumer, Sven Reiche, Holger Freese, Jan Schinköthe, Sandra Diederich, Jens P. Teifke, Mario Lorenz, Rene Stenzel
article en

Abstract

ABSTRACT Airborne disinfection of high-containment facilities is mandatory for safe operations. However, sewage vent air—particularly in large-animal experimental units—can represent a critical gap and is typically not considered in the design of high-efficiency particulate air (HEPA) filter systems. Here, we present an engineering design enabling HEPA filtration of sewage vent air from primary biological containments, including large-animal facilities and necropsy suites. We additionally evaluated vaporized hydrogen peroxide (vH 2 O 2 ) fumigation as an airborne disinfection approach. Disinfection efficacy was determined by quantitative carrier testing using commercial spore carriers (CSC) coated with 10 6 spores of Geobacillus stearothermophilus and compared with germ carriers coated with surrogate viruses, mycobacteria, and other spores. Temperature, relative humidity (RH), and vH 2 O 2 concentration were monitored in real time to define process parameters and validate protocols targeting ≥4 log 10 reduction. Inactivation efficacy differed substantially among challenge agents: CSC were least resistant to inactivation, whereas murine norovirus (MNV) on germ carriers was most challenging to inactivate. At medium-high vH 2 O 2 concentrations (up to 520 parts per million [ppm]), increasing RH was the dominant driver of inactivation. Based on these data, we developed a biphasic disinfection cycle maintaining a saturated humidity environment with ~35% H 2 O 2 for ≥10 h, achieving ≥4 log 10 reduction of MNV infectivity and G. stearothermophilus spore viability on germ carriers. Overall, vH 2 O 2 under high-to-saturated RH is an effective means to disinfect technical infrastructure in biological containment settings handling high-consequence pathogens. IMPORTANCE Vent air from sewage systems in biological containment facilities where large animals are kept should be considered a contaminated waste stream. Therefore, effective high-efficiency particulate air (HEPA) filter systems that prevent mold or other moisture-related deterioration of the filters need to be installed. Airborne vaporized hydrogen peroxide (vH 2 O 2 ) is an appropriate method to decontaminate these complex HEPA filter systems. High to saturated humidity is required for virucidal and sporicidal efficacy under medium to high concentration of vH 2 O 2 . Commercially available spore carriers are artificial in design, resulting in lower resistance to inactivation compared to custom germ carriers coated with non-enveloped viruses and thus should be avoided as read-out (validation means) by the biosafety community working with high-consequence pathogens in primary containments.

Applied and Environmental Microbiology
Friedrich-Loeffler-Institut (DE), Novel (United States) (US)
Clean water and sanitation
Openalex Percentile: Top 11%
Viral gastroenteritis research and epidemiology
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.