Beyond PUE: A Boundary-Aware Primary-Energy Framework for Evaluating Self- Powered Computing Infrastructure, with Application to a Hybrid Offshore Floating Data Center

Abstract Power usage effectiveness (PUE) is the dominant data-center sustainability metric, but it is defined only over the facility boundary: cooling and auxiliary overhead relative to the IT load. For self-powered infrastructure generating its own electricity on site, this boundary excludes exactly the losses—fuel-to-electricity conversion and any carbon-capture parasitic load—that determine whether total energy use is actually efficient. In this study, the hypothesis that facility-level PUE can systematically overestimate self-powered infrastructure sustainability is tested, and a boundary-aware primary-energy framework (η_primary = η_cycle × (1 − CCS penalty)/PUE) is developed to clarify that gap. The framework is applied to a proposal-stage architecture, the Hybrid Seabed-Energy Floating Data Center (HSE-FDC), offshore gas turbines, a wave-energy-converter array, carbon capture, and passive marine cooling, which had a PUE of approximately 1.04 with negligible grid dependency. Using literature-grounded parameters, the case study yields a plausible facility PUE of 1.08–1.09, which is comparable to that of real benchmarks, whereas the wave array contributes under 1.2% of the average power, which is far short of a genuine hybrid baseload. Critically, this favorable facility PUE corresponds to a primary energy efficiency of only 25.5–38.7%, below a conventional grid-tied facility (43.0%) and dramatically below a renewable-grid-tied facility (93.5%): a favorable facility PUE does not, by itself, indicate favorable total energy efficiency once onsite generation is included. The architecture's individual technologies are each already commercialized elsewhere; this study's contribution is the general framework and the demonstration that it changes the sustainability conclusion for a real architecture, generalizing to other off-grid contexts.

Authors

Publication Details

Journal
Research Square
Published
2026-11-03
DOI
https://doi.org/10.21203/rs.3.rs-10949065/v1
Primary Topic
Green IT and Sustainability
Type
preprint
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
preprint

Beyond PUE: A Boundary-Aware Primary-Energy Framework for Evaluating Self- Powered Computing Infrastructure, with Application to a Hybrid Offshore Floating Data Center

Leon Sandler
Research Square
Green IT and Sustainability
preprint

Beyond PUE: A Boundary-Aware Primary-Energy Framework for Evaluating Self- Powered Computing Infrastructure, with Application to a Hybrid Offshore Floating Data Center

Leon Sandler
preprint en

Abstract

Abstract Power usage effectiveness (PUE) is the dominant data-center sustainability metric, but it is defined only over the facility boundary: cooling and auxiliary overhead relative to the IT load. For self-powered infrastructure generating its own electricity on site, this boundary excludes exactly the losses—fuel-to-electricity conversion and any carbon-capture parasitic load—that determine whether total energy use is actually efficient. In this study, the hypothesis that facility-level PUE can systematically overestimate self-powered infrastructure sustainability is tested, and a boundary-aware primary-energy framework (η_primary = η_cycle × (1 − CCS penalty)/PUE) is developed to clarify that gap. The framework is applied to a proposal-stage architecture, the Hybrid Seabed-Energy Floating Data Center (HSE-FDC), offshore gas turbines, a wave-energy-converter array, carbon capture, and passive marine cooling, which had a PUE of approximately 1.04 with negligible grid dependency. Using literature-grounded parameters, the case study yields a plausible facility PUE of 1.08–1.09, which is comparable to that of real benchmarks, whereas the wave array contributes under 1.2% of the average power, which is far short of a genuine hybrid baseload. Critically, this favorable facility PUE corresponds to a primary energy efficiency of only 25.5–38.7%, below a conventional grid-tied facility (43.0%) and dramatically below a renewable-grid-tied facility (93.5%): a favorable facility PUE does not, by itself, indicate favorable total energy efficiency once onsite generation is included. The architecture's individual technologies are each already commercialized elsewhere; this study's contribution is the general framework and the demonstration that it changes the sustainability conclusion for a real architecture, generalizing to other off-grid contexts.

Research Square
Affordable and clean energy, Climate action, Industry, innovation and infrastructure
Green IT and Sustainability
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon
Beyond PUE: A Boundary-Aware Primary-Energy Framework for Evaluating Self- Powered Computing Infrastructure, with Application to a Hybrid Offshore Floating Data Center — Leon Sandler · Research Square (2026) | TGRS Research Map | TGRS