In-situ evaluation of an interior suspended-film multi-cavity glazing retrofit for existing curtain-wall buildings

This study proposed a glazing retrofit system (hereafter GR system) in which an interior suspended-film unit was added to an existing Low-E double-glazed curtain-wall assembly to form a multi-cavity assembly, and experimentally evaluated its short-term winter thermal performance. Unlike previous studies that relied on laboratory hot-box measurements or numerical simulation, this work provides in-situ measurement, using the average method of ISO 9869-1, of center-of-glazing thermal transmittance, surface-temperature distributions, and heat-mode energy consumption under real winter boundary conditions. The retrofitted assembly comprised five layers with four cavities and two low-emissivity coatings acting in series. Two adjacent full-scale test rooms (3.6 m × 5.4 m × 2.7 m) in Goyang, South Korea, were monitored simultaneously over 72 h under a controlled heating schedule of 8 h per day, with semi-outdoor air temperatures from −9.38 to −1.49 °C. The glazed façade faced an unconditioned semi-outdoor space and received no direct solar radiation, thereby minimizing the influence of direct solar gains and allowing the conductive component to be evaluated separately. The measured center-of-glazing U-value decreased from 1.738 to 0.347 W/m 2 ·K, a reduction of 80.0%. This reduction applies to the center of glazing only; the existing aluminum frame was unchanged, so the improvement at whole-window level is smaller. The indoor-side glazing surface temperature increased by 2.4 K at the center and 3.0 K at the edge during heating, while the average indoor-side frame surface temperature decreased by 2.6 K. Whole-window heat-loss decomposition indicated that the retained frame became the single largest heat-loss path after the retrofit and bounds the benefit obtainable from a glazing-only intervention. Daily heat-mode energy use was reduced by 10.9%, and by 12.1% after normalization for the indoor-outdoor temperature difference; an indicative annual simulation for a reference office building, not validated against these measurements, gives a heating energy reduction of 11.5–15.8%.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2026-08-27
DOI
https://doi.org/10.1016/j.csite.2026.108469
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

In-situ evaluation of an interior suspended-film multi-cavity glazing retrofit for existing curtain-wall buildings

Kyungjoo Cho, Taeyeon Kim
Case Studies in Thermal Engineering
Building Energy and Comfort Optimization
article

In-situ evaluation of an interior suspended-film multi-cavity glazing retrofit for existing curtain-wall buildings

Kyungjoo Cho, Taeyeon Kim
article en

Abstract

This study proposed a glazing retrofit system (hereafter GR system) in which an interior suspended-film unit was added to an existing Low-E double-glazed curtain-wall assembly to form a multi-cavity assembly, and experimentally evaluated its short-term winter thermal performance. Unlike previous studies that relied on laboratory hot-box measurements or numerical simulation, this work provides in-situ measurement, using the average method of ISO 9869-1, of center-of-glazing thermal transmittance, surface-temperature distributions, and heat-mode energy consumption under real winter boundary conditions. The retrofitted assembly comprised five layers with four cavities and two low-emissivity coatings acting in series. Two adjacent full-scale test rooms (3.6 m × 5.4 m × 2.7 m) in Goyang, South Korea, were monitored simultaneously over 72 h under a controlled heating schedule of 8 h per day, with semi-outdoor air temperatures from −9.38 to −1.49 °C. The glazed façade faced an unconditioned semi-outdoor space and received no direct solar radiation, thereby minimizing the influence of direct solar gains and allowing the conductive component to be evaluated separately. The measured center-of-glazing U-value decreased from 1.738 to 0.347 W/m 2 ·K, a reduction of 80.0%. This reduction applies to the center of glazing only; the existing aluminum frame was unchanged, so the improvement at whole-window level is smaller. The indoor-side glazing surface temperature increased by 2.4 K at the center and 3.0 K at the edge during heating, while the average indoor-side frame surface temperature decreased by 2.6 K. Whole-window heat-loss decomposition indicated that the retained frame became the single largest heat-loss path after the retrofit and bounds the benefit obtainable from a glazing-only intervention. Daily heat-mode energy use was reduced by 10.9%, and by 12.1% after normalization for the indoor-outdoor temperature difference; an indicative annual simulation for a reference office building, not validated against these measurements, gives a heating energy reduction of 11.5–15.8%.

Case Studies in Thermal EngineeringVol. 86
Yonsei University (KR), Korea Institute of Civil Engineering and Building Technology (KR)
Ministry of Science and ICT, South Korea
Affordable and clean energy
Openalex Percentile: Top 14%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.