In-situ load testing and finite element analysis of a damaged reinforced concrete flat plate slab in a tall building

Abstract This study provides a detailed case analysis of a reinforced concrete flat plate slab with localized damage in a 25-story high-rise. A poorly hardened concrete layer under the soffit raised immediate concerns about structural safety, prompting a thorough evaluation in accordance with ACI 318-25. A controlled 24-h monotonic load test was conducted using sandbags, with real-time deflection data recorded. Results indicated a maximum deflection of 5.70 mm and a residual deflection of 0.62 mm—both within acceptable limits per code. No crack growth or signs of ongoing deterioration were seen during visual checks after the test. Nonlinear finite element analyses in ABAQUS used the concrete damaged plasticity model with test-based concrete properties and no calibration. On the actual supports, the analysis gave 4.66 mm at full load against 5.12 mm measured, whereas clamped panel edges gave only 0.89–2.19 mm. Although the slab performed well during testing, repair of the deteriorated soffit is advised to address possible long-term issues. This case study offers insights into evaluating flat plate systems with localized damage, linking field diagnostics with analytical models.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2026-11-11
DOI
https://doi.org/10.1038/s41598-026-79639-z
Primary Topic
Structural Behavior of Reinforced Concrete
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
article

In-situ load testing and finite element analysis of a damaged reinforced concrete flat plate slab in a tall building

Raquib Ahsan, Md. Rifat Bin Ahmed Majumdar
1 links
Scientific Reports
Structural Behavior of Reinforced Concrete
article

In-situ load testing and finite element analysis of a damaged reinforced concrete flat plate slab in a tall building

Raquib Ahsan, Md. Rifat Bin Ahmed Majumdar
article en

Abstract

Abstract This study provides a detailed case analysis of a reinforced concrete flat plate slab with localized damage in a 25-story high-rise. A poorly hardened concrete layer under the soffit raised immediate concerns about structural safety, prompting a thorough evaluation in accordance with ACI 318-25. A controlled 24-h monotonic load test was conducted using sandbags, with real-time deflection data recorded. Results indicated a maximum deflection of 5.70 mm and a residual deflection of 0.62 mm—both within acceptable limits per code. No crack growth or signs of ongoing deterioration were seen during visual checks after the test. Nonlinear finite element analyses in ABAQUS used the concrete damaged plasticity model with test-based concrete properties and no calibration. On the actual supports, the analysis gave 4.66 mm at full load against 5.12 mm measured, whereas clamped panel edges gave only 0.89–2.19 mm. Although the slab performed well during testing, repair of the deteriorated soffit is advised to address possible long-term issues. This case study offers insights into evaluating flat plate systems with localized damage, linking field diagnostics with analytical models.

Scientific Reports
Bangladesh University of Engineering and Technology (BD)
Structural Behavior of Reinforced Concrete
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Laika access coming soon