Device-Level Sensing Availability and MQTT Application-Response Latency in an openHAB-Based Smart-Building System

Smart-building systems need reliable sensing, long-term storage, and remote control, but many studies mix up fast network response with slow physical changes in the building. We report measurements from an openHAB deployment at University Lab 1 and University Lab 2 in Greece over 19 months (April 2024–October 2025), with Z-Wave and ZigBee devices and Parquet exports for offline analysis. We treat sensing availability, Message Queuing Telemetry Transport (MQTT) command latency, and heating, ventilation, and air conditioning (HVAC) behavior as separate questions. In March–June 2024, raw record-level temperature field availability was 79.7% and 74.2% at University Lab 1 and University Lab 2, respectively, increasing to 99.7% and 98.5% after the <30 min linear field interpolation used in golden-dataset construction; assessable device-month cadence-normalized reading-count ratios were far lower (7.9% temperature and 13.0% humidity under the 300 s assumption at University Lab 1; humidity 7.8–26.0% across 180–600 s), reflecting heterogeneous archival participation rather than a fully populated expected-cadence denominator over the full archive span. In May–June 2024, 1247 MQTT commands yielded 1246 successful correlated responses; the archived application log contained no repeated correlation identifiers or duplicate response records (broker DUP flags are not archived); median, p90, and p99 latencies were 287 ms, 487 ms, and 1.66 s. These times describe the MQTT–edge-agent–openHAB path only, not physical device action. HVAC figures are illustrative; we do not infer settling times. The results show why availability metrics, archive denominators, and response-time boundaries must be defined separately in smart-building evaluations.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2026-08-18
DOI
https://doi.org/10.3390/electronics15163685
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Device-Level Sensing Availability and MQTT Application-Response Latency in an openHAB-Based Smart-Building System

Sotirios Tsakalidis, G.V. Tsoulos, Georgia Athanasiadou, Dimitrios Kontaxis
Electronics
Building Energy and Comfort Optimization
article

Device-Level Sensing Availability and MQTT Application-Response Latency in an openHAB-Based Smart-Building System

Sotirios Tsakalidis, G.V. Tsoulos, Georgia Athanasiadou, Dimitrios Kontaxis
article en

Abstract

Smart-building systems need reliable sensing, long-term storage, and remote control, but many studies mix up fast network response with slow physical changes in the building. We report measurements from an openHAB deployment at University Lab 1 and University Lab 2 in Greece over 19 months (April 2024–October 2025), with Z-Wave and ZigBee devices and Parquet exports for offline analysis. We treat sensing availability, Message Queuing Telemetry Transport (MQTT) command latency, and heating, ventilation, and air conditioning (HVAC) behavior as separate questions. In March–June 2024, raw record-level temperature field availability was 79.7% and 74.2% at University Lab 1 and University Lab 2, respectively, increasing to 99.7% and 98.5% after the <30 min linear field interpolation used in golden-dataset construction; assessable device-month cadence-normalized reading-count ratios were far lower (7.9% temperature and 13.0% humidity under the 300 s assumption at University Lab 1; humidity 7.8–26.0% across 180–600 s), reflecting heterogeneous archival participation rather than a fully populated expected-cadence denominator over the full archive span. In May–June 2024, 1247 MQTT commands yielded 1246 successful correlated responses; the archived application log contained no repeated correlation identifiers or duplicate response records (broker DUP flags are not archived); median, p90, and p99 latencies were 287 ms, 487 ms, and 1.66 s. These times describe the MQTT–edge-agent–openHAB path only, not physical device action. HVAC figures are illustrative; we do not infer settling times. The results show why availability metrics, archive denominators, and response-time boundaries must be defined separately in smart-building evaluations.

ElectronicsVol. 15(16)
University of Peloponnese (GR)
Openalex Percentile: Top 13%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Device-Level Sensing Availability and MQTT Application-Response Latency in an openHAB-Based Smart-Building System — Sotirios Tsakalidis, G.V. Tsoulos, et al. · Electronics (2026) | TGRS Research Map | TGRS