Response-Driven Online Emergency Control for Power System Transient Stability via ConvLSTM-Based sBTTC Sensitivity Prediction

With increasing renewable and power-electronic penetration, emergency control must convert early post-fault measurements into feasible actions within a short latency budget. This paper proposes a response-driven online framework that uses the simplified branch transient transmission capacity (sBTTC) as a physically interpretable interface between causal stability forecasting, action-response prediction, and constrained control. A preceding masked Informer forecasts the no-control all-branch sBTTC trajectories from the first 1.00 s of measured response; a ConvLSTM then predicts generator-tripping recovery and the recovery associated with four load-shedding levels. These predictions are embedded in a weighted mixed-integer piecewise-linear model with stability-recovery, action-bound, and power-balance constraints. On the studied 100-bus renewable-rich AC/DC system, ConvLSTM achieved an RMSE of 7.193×10−3 and an MAE of 5.674×10−3 with 69.16 ms inference time. Its inference was 66.42% faster than Informer, while its RMSE was only 2.06% higher; relative to conventional LSTM, its RMSE and MAE were reduced by 28.21% and 21.53%, respectively. Across 62 grouped out-of-sample disturbances, the validation results give a 96.77% control success rate. In the representative disturbance, 900 MW of generation tripping and 740 MW of load shedding restored the nonlinear terminal sBTTC to 0.998, and the command was issued 1.36 s after fault inception. The framework provides an auditable forecast–response–decision chain; its additive approximation is restricted to the validated action range and uses an empirical 0.05 sBTTC recovery margin selected to exceed the observed 95th-percentile absolute error; this margin is not interpreted as a worst-case error bound.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2026-08-18
DOI
https://doi.org/10.3390/electronics15163696
Primary Topic
Power System Optimization and Stability
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Response-Driven Online Emergency Control for Power System Transient Stability via ConvLSTM-Based sBTTC Sensitivity Prediction

Xianglian Guan, Yongcan Wang, Peng Shi, Zongsheng Zheng et al.
Electronics
Power System Optimization and Stability
article

Response-Driven Online Emergency Control for Power System Transient Stability via ConvLSTM-Based sBTTC Sensitivity Prediction

Xianglian Guan, Yongcan Wang, Peng Shi, Zongsheng Zheng, Chufang Xu, Wei Liu, Guocheng Qu, Xi Ye
article en

Abstract

With increasing renewable and power-electronic penetration, emergency control must convert early post-fault measurements into feasible actions within a short latency budget. This paper proposes a response-driven online framework that uses the simplified branch transient transmission capacity (sBTTC) as a physically interpretable interface between causal stability forecasting, action-response prediction, and constrained control. A preceding masked Informer forecasts the no-control all-branch sBTTC trajectories from the first 1.00 s of measured response; a ConvLSTM then predicts generator-tripping recovery and the recovery associated with four load-shedding levels. These predictions are embedded in a weighted mixed-integer piecewise-linear model with stability-recovery, action-bound, and power-balance constraints. On the studied 100-bus renewable-rich AC/DC system, ConvLSTM achieved an RMSE of 7.193×10−3 and an MAE of 5.674×10−3 with 69.16 ms inference time. Its inference was 66.42% faster than Informer, while its RMSE was only 2.06% higher; relative to conventional LSTM, its RMSE and MAE were reduced by 28.21% and 21.53%, respectively. Across 62 grouped out-of-sample disturbances, the validation results give a 96.77% control success rate. In the representative disturbance, 900 MW of generation tripping and 740 MW of load shedding restored the nonlinear terminal sBTTC to 0.998, and the command was issued 1.36 s after fault inception. The framework provides an auditable forecast–response–decision chain; its additive approximation is restricted to the validated action range and uses an empirical 0.05 sBTTC recovery margin selected to exceed the observed 95th-percentile absolute error; this margin is not interpreted as a worst-case error bound.

ElectronicsVol. 15(16)
Sichuan University (CN), Science and Technology Department of Sichuan Province (CN)
Affordable and clean energy
Openalex Percentile: Top 18%
Power System Optimization and Stability
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.