Performance Evaluation and Carbon Emission Reduction Analysis of a Coupled Photovoltaic Thermal and Air Source Heat Pump Heating System in Office Buildings

PV/T collectors and Air Source Heat Pump (ASHP) are widely studied for building heating, but solar intermittency and ASHP low-temperature frosting limit their large-scale deployment. A novel PV/T-ASHP coupled heating system is proposed to cut building carbon emissions and relieve ASHP performance degradation in cold zones. Circulating water cools PV/T panels to boost power generation, and the warmed water preheats ASHP evaporator inlet air to reduce frosting and defrosting frequency. With a Xi’an office building as the research object, validated TRNSYS 18.0 models are established for comparative analysis with conventional systems and cross-climate evaluation in Xi’an, Beijing, Shanghai and Chengdu. Results show the new system lifts PV/T combined efficiency by 17.56%, reduces energy consumption by 19.9%, and achieves an average COP of 3.2. Across climate zones, its COP rises 11.5–24.6% and 50-year carbon emissions fall 16.4–26.2%, supporting low-carbon heating promotion for office buildings.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-08-18
DOI
https://doi.org/10.3390/en19163867
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance Evaluation and Carbon Emission Reduction Analysis of a Coupled Photovoltaic Thermal and Air Source Heat Pump Heating System in Office Buildings

Yabin Jin, Zizhen Huang, Wenhan Song, Yuxin Zheng
Energies
Geothermal Energy Systems and Applications
article

Performance Evaluation and Carbon Emission Reduction Analysis of a Coupled Photovoltaic Thermal and Air Source Heat Pump Heating System in Office Buildings

Yabin Jin, Zizhen Huang, Wenhan Song, Yuxin Zheng
article en

Abstract

PV/T collectors and Air Source Heat Pump (ASHP) are widely studied for building heating, but solar intermittency and ASHP low-temperature frosting limit their large-scale deployment. A novel PV/T-ASHP coupled heating system is proposed to cut building carbon emissions and relieve ASHP performance degradation in cold zones. Circulating water cools PV/T panels to boost power generation, and the warmed water preheats ASHP evaporator inlet air to reduce frosting and defrosting frequency. With a Xi’an office building as the research object, validated TRNSYS 18.0 models are established for comparative analysis with conventional systems and cross-climate evaluation in Xi’an, Beijing, Shanghai and Chengdu. Results show the new system lifts PV/T combined efficiency by 17.56%, reduces energy consumption by 19.9%, and achieves an average COP of 3.2. Across climate zones, its COP rises 11.5–24.6% and 50-year carbon emissions fall 16.4–26.2%, supporting low-carbon heating promotion for office buildings.

EnergiesVol. 19(16)
Xi'an Aeronautical University (CN)
Affordable and clean energy
Openalex Percentile: Top 26%
Geothermal Energy Systems and Applications
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.