Identification of the Hydronic Index Circuit and Dynamic Balancing in Variable-Flow Chilled Water Systems

In multi-story variable-flow chilled water (CHW) networks, improper sensor positioning and misidentification of the system index circuit lead to severe hydraulic starvation at remote terminals or substantial auxiliary pumping energy waste. This paper presents empirical field data from a commercial high-rise facility in the Eastern Province, Saudi Arabia, detailing a systematic step-by-step diagnostic procedure for identifying the true index circuit (AHU-14) and executing dynamic balancing. By relocating the main differential pressure (DP) control sensor to a 2/3 location along the main riser and calibrating Pressure Independent Control Valves (PICVs), design flow was fully restored to starved branches while reducing pump power draw by 24.3% (142 kW to 107.5 kW). All specific corporate and facility identifiers are anonymized per standard academic disclosure protocols.

Authors

Institutions

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-07-28
DOI
https://doi.org/10.5281/zenodo.21644887
Primary Topic
Water Systems and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Identification of the Hydronic Index Circuit and Dynamic Balancing in Variable-Flow Chilled Water Systems

Younes Al Haj
Zenodo (CERN European Organization for Nuclear Research)
Water Systems and Optimization
article

Identification of the Hydronic Index Circuit and Dynamic Balancing in Variable-Flow Chilled Water Systems

Younes Al Haj
article en

Abstract

In multi-story variable-flow chilled water (CHW) networks, improper sensor positioning and misidentification of the system index circuit lead to severe hydraulic starvation at remote terminals or substantial auxiliary pumping energy waste. This paper presents empirical field data from a commercial high-rise facility in the Eastern Province, Saudi Arabia, detailing a systematic step-by-step diagnostic procedure for identifying the true index circuit (AHU-14) and executing dynamic balancing. By relocating the main differential pressure (DP) control sensor to a 2/3 location along the main riser and calibrating Pressure Independent Control Valves (PICVs), design flow was fully restored to starved branches while reducing pump power draw by 24.3% (142 kW to 107.5 kW). All specific corporate and facility identifiers are anonymized per standard academic disclosure protocols.

Zenodo (CERN European Organization for Nuclear Research)
New England Biolabs (United Kingdom) (GB)
Openalex Percentile: Top 14%
Water Systems and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.