Airtightness of School Classrooms in Spain: Field Measurements and Retrofit Implications

This study characterises the airtightness of school classrooms in several Spanish educational centres using blower-door measurements (ISO 9972:2015). Building envelope airtightness governs uncontrolled air infiltration and plays a central role in indoor air quality (IAQ): excessively permeable envelopes increase the ingress of outdoor pollutants such as PM2.5, while highly airtight classrooms without adequate mechanical ventilation may accumulate indoor CO2 and thermal discomfort. In Mediterranean climates, where mechanical ventilation is not systematically installed in schools, uncontrolled infiltration frequently becomes the dominant air renewal mechanism during the heating season. The measured classrooms show a mean n50 of 9.08 h−1 (range: 4.32–22.67 h−1), placing them at an intermediate level in the international literature. High within-school variability was identified, indicating that single-classroom measurements may be insufficient to represent building-level airtightness. External façade area showed the strongest exploratory association with n50 (Spearman ρ = 0.663, p = 0.037), but the small, non-random sample does not support generalising this relationship beyond the measured classrooms. The paired comparison in Centre C4 did not suggest an airtightness improvement beyond measurement uncertainty after the specific ETICS intervention, while the C5 case illustrates the potential influence of unsealed service penetrations. Overall, the observations point to windows, junctions and service penetrations as priority locations for diagnosis and targeted sealing, to be verified in larger and more diverse samples.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2026-07-27
DOI
https://doi.org/10.3390/buildings16152979
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Airtightness of School Classrooms in Spain: Field Measurements and Retrofit Implications

Jésica Fernández-Agüera, Julio Bros-Williamson, Victoria Domínguez Ruiz, Samuel Domínguez-Amarillo
Buildings
Building Energy and Comfort Optimization
article

Airtightness of School Classrooms in Spain: Field Measurements and Retrofit Implications

Jésica Fernández-Agüera, Julio Bros-Williamson, Victoria Domínguez Ruiz, Samuel Domínguez-Amarillo
article en

Abstract

This study characterises the airtightness of school classrooms in several Spanish educational centres using blower-door measurements (ISO 9972:2015). Building envelope airtightness governs uncontrolled air infiltration and plays a central role in indoor air quality (IAQ): excessively permeable envelopes increase the ingress of outdoor pollutants such as PM2.5, while highly airtight classrooms without adequate mechanical ventilation may accumulate indoor CO2 and thermal discomfort. In Mediterranean climates, where mechanical ventilation is not systematically installed in schools, uncontrolled infiltration frequently becomes the dominant air renewal mechanism during the heating season. The measured classrooms show a mean n50 of 9.08 h−1 (range: 4.32–22.67 h−1), placing them at an intermediate level in the international literature. High within-school variability was identified, indicating that single-classroom measurements may be insufficient to represent building-level airtightness. External façade area showed the strongest exploratory association with n50 (Spearman ρ = 0.663, p = 0.037), but the small, non-random sample does not support generalising this relationship beyond the measured classrooms. The paired comparison in Centre C4 did not suggest an airtightness improvement beyond measurement uncertainty after the specific ETICS intervention, while the C5 case illustrates the potential influence of unsealed service penetrations. Overall, the observations point to windows, junctions and service penetrations as priority locations for diagnosis and targeted sealing, to be verified in larger and more diverse samples.

BuildingsVol. 16(15)
Universidad de Sevilla (ES), University of Edinburgh (GB)
Climate action
Openalex Percentile: Top 12%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.