Experimental Study on the Fire Hazard of Flat-Laid Rooftop Photovoltaic Systems Under Localized External Fire Exposure: Implications for High-Rise Building Applications

As rooftop photovoltaic (PV) systems are increasingly deployed on taller buildings and across a wider range of building applications, localized overheating or initial fires caused by electrical faults, combustible roof-covering materials, or maintenance-related ignition sources may affect PV modules and contribute to subsequent fire spread over the rooftop system. In this study, a full-scale fire experiment was conducted on a flat-laid rooftop PV system using a nominal 100 kW n-heptane pan fire as a controlled localized external fire source to investigate the fire development and escalation mechanism of the system. The results show that the fire hazard was first and primarily concentrated in the confined under-panel space: the average cavity peak temperature of the ignited array reached 684.0 °C, with a local maximum of 853.4 °C, both significantly higher than the maximum upper-surface center temperature of 370.7 °C. The involvement of the waterproofing membrane in combustion was the key amplifying mechanism driving the transition from localized heating to a sustained high-temperature event; the average cavity temperature exceeded 500 °C after 234 s and remained above this threshold for approximately 201 s, with an average cavity heat accumulation index of 178.1 × 103 °C·s. Compared with the lower upper-surface center measuring points, hazardous temperatures beneath the modules were reached earlier by 149, 193 and 247 s at the thresholds of 50, 100 and 200 °C, respectively. Under the tested configuration, these findings provide engineering insights for fire-risk identification, early monitoring, and fire-safe design of flat-laid rooftop PV systems in high-rise building applications.

Authors

Institutions

Publication Details

Journal
Fire
Published
2026-07-24
DOI
https://doi.org/10.3390/fire9080316
Primary Topic
Fire dynamics and safety research
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental Study on the Fire Hazard of Flat-Laid Rooftop Photovoltaic Systems Under Localized External Fire Exposure: Implications for High-Rise Building Applications

S M Liu, Ping Fang, Xi Zhang, Songtao Liu et al.
Fire
Fire dynamics and safety research
article

Experimental Study on the Fire Hazard of Flat-Laid Rooftop Photovoltaic Systems Under Localized External Fire Exposure: Implications for High-Rise Building Applications

S M Liu, Ping Fang, Xi Zhang, Songtao Liu, Yuehe Mao, Ruihong Pan, Lihong Zhao, Xiaolin Yang
article en

Abstract

As rooftop photovoltaic (PV) systems are increasingly deployed on taller buildings and across a wider range of building applications, localized overheating or initial fires caused by electrical faults, combustible roof-covering materials, or maintenance-related ignition sources may affect PV modules and contribute to subsequent fire spread over the rooftop system. In this study, a full-scale fire experiment was conducted on a flat-laid rooftop PV system using a nominal 100 kW n-heptane pan fire as a controlled localized external fire source to investigate the fire development and escalation mechanism of the system. The results show that the fire hazard was first and primarily concentrated in the confined under-panel space: the average cavity peak temperature of the ignited array reached 684.0 °C, with a local maximum of 853.4 °C, both significantly higher than the maximum upper-surface center temperature of 370.7 °C. The involvement of the waterproofing membrane in combustion was the key amplifying mechanism driving the transition from localized heating to a sustained high-temperature event; the average cavity temperature exceeded 500 °C after 234 s and remained above this threshold for approximately 201 s, with an average cavity heat accumulation index of 178.1 × 103 °C·s. Compared with the lower upper-surface center measuring points, hazardous temperatures beneath the modules were reached earlier by 149, 193 and 247 s at the thresholds of 50, 100 and 200 °C, respectively. Under the tested configuration, these findings provide engineering insights for fire-risk identification, early monitoring, and fire-safe design of flat-laid rooftop PV systems in high-rise building applications.

FireVol. 9(8)
Harbin Institute of Technology (CN), China Academy of Building Research (CN), Henan Polytechnic University (CN)
Sustainable cities and communities
Openalex Percentile: Top 9%
Fire dynamics and safety research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.