Single-Phase Ground Fault Line Selection of Wind Farm Collector Line Based on Transient Zero-Mode Current

Faults in wind farm multi-branch collector lines produce weak transient zero-mode current characteristics, rendering conventional amplitude- and phase-based selection methods ineffective. To address this, the paper proposes a faulty feeder selection method that integrates transient zero-mode differential current with the S-transform. A π-type zero-mode network is first established to reveal the composition and variation in transient zero-mode current under different operating conditions. Theoretical analysis demonstrates a distinguishable feature—the sending-end current of the faulted branch exhibits significantly larger amplitude and opposite polarity compared with non-faulted branches—while the end-side currents near wind turbines remain highly similar and thus hinder accurate selection. Motivated by this disparity, the adaptive time–frequency focusing property of the S-transform is exploited to extract high-frequency energy and differential signatures within the optimal band, from which a dual criterion consisting of the differential feature quantity Dm and the time–frequency energy Em is constructed. The method is validated on a 35 kV DFIG-based wind farm collector line model built in PSCAD/EMTDC and benchmarked against the wavelet transform and empirical mode decomposition under various operating conditions. The results confirm that the proposed method accurately distinguishes bus faults from branch faults, reliably identifies the faulty feeder, and remains unaffected by fault distance and operating conditions, demonstrating strong robustness and anti-interference capability.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2026-07-24
DOI
https://doi.org/10.3390/electronics15153264
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Single-Phase Ground Fault Line Selection of Wind Farm Collector Line Based on Transient Zero-Mode Current

Zhipeng Gao, Yue Wang, Huida Duan, Song Bai et al.
Electronics
Power Systems Fault Detection
article

Single-Phase Ground Fault Line Selection of Wind Farm Collector Line Based on Transient Zero-Mode Current

Zhipeng Gao, Yue Wang, Huida Duan, Song Bai, Ying Zhao, Shihao Zhao
article en

Abstract

Faults in wind farm multi-branch collector lines produce weak transient zero-mode current characteristics, rendering conventional amplitude- and phase-based selection methods ineffective. To address this, the paper proposes a faulty feeder selection method that integrates transient zero-mode differential current with the S-transform. A π-type zero-mode network is first established to reveal the composition and variation in transient zero-mode current under different operating conditions. Theoretical analysis demonstrates a distinguishable feature—the sending-end current of the faulted branch exhibits significantly larger amplitude and opposite polarity compared with non-faulted branches—while the end-side currents near wind turbines remain highly similar and thus hinder accurate selection. Motivated by this disparity, the adaptive time–frequency focusing property of the S-transform is exploited to extract high-frequency energy and differential signatures within the optimal band, from which a dual criterion consisting of the differential feature quantity Dm and the time–frequency energy Em is constructed. The method is validated on a 35 kV DFIG-based wind farm collector line model built in PSCAD/EMTDC and benchmarked against the wavelet transform and empirical mode decomposition under various operating conditions. The results confirm that the proposed method accurately distinguishes bus faults from branch faults, reliably identifies the faulty feeder, and remains unaffected by fault distance and operating conditions, demonstrating strong robustness and anti-interference capability.

ElectronicsVol. 15(15)
Changchun Institute of Technology (CN)
Affordable and clean energy
Openalex Percentile: Top 11%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Single-Phase Ground Fault Line Selection of Wind Farm Collector Line Based on Transient Zero-Mode Current — Zhipeng Gao, Yue Wang, et al. · Electronics (2026) | TGRS Research Map | TGRS