Commercial refrigeration systems represent some of the largest energy consumers in supermarkets, and therefore particular attention needs to be paid to increasing energy efficiency to reduce overall energy consumption and meet climate goals by 2030. This study investigates the performance of a CO2 (R744) commercial refrigeration system with evaporators operating alternately in dry and flooded modes. This operation is possible due to a particular adjustment using liquid sensors installed in the middle of both low-temperature (LT) and medium-temperature (MT) liquid separators, which transmit information to the controllers that regulate the compressor rack and evaporators, to switch from dry to flooded operation when the liquid level rises and vice versa when the level drops. The results show that the correct regulation of the system of 50% with 6K superheat operation and 50% with 3K superheat operation on MT evaporators, respectively, and 50% with 6K superheat operation and 50% with 4K superheat operation on LT evaporators leads to a reduction of energy consumption compared to 100% operation of all evaporators with 6K superheat by 6.9% per year for the compressor rack.

Authors

Institutions

Publication Details

Journal
Technologies
Published
2026-07-16
DOI
https://doi.org/10.3390/technologies14070436
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Impact of Evaporator Operating Mode Switching on the Performance of CO2 Commercial Refrigeration Systems

Ion V. Ion, Costel Ungureanu, Ionuț Dumitriu
Technologies
Refrigeration and Air Conditioning Technologies
article

Impact of Evaporator Operating Mode Switching on the Performance of CO2 Commercial Refrigeration Systems

Ion V. Ion, Costel Ungureanu, Ionuț Dumitriu
article en

Abstract

Commercial refrigeration systems represent some of the largest energy consumers in supermarkets, and therefore particular attention needs to be paid to increasing energy efficiency to reduce overall energy consumption and meet climate goals by 2030. This study investigates the performance of a CO2 (R744) commercial refrigeration system with evaporators operating alternately in dry and flooded modes. This operation is possible due to a particular adjustment using liquid sensors installed in the middle of both low-temperature (LT) and medium-temperature (MT) liquid separators, which transmit information to the controllers that regulate the compressor rack and evaporators, to switch from dry to flooded operation when the liquid level rises and vice versa when the level drops. The results show that the correct regulation of the system of 50% with 6K superheat operation and 50% with 3K superheat operation on MT evaporators, respectively, and 50% with 6K superheat operation and 50% with 4K superheat operation on LT evaporators leads to a reduction of energy consumption compared to 100% operation of all evaporators with 6K superheat by 6.9% per year for the compressor rack.

TechnologiesVol. 14(7)
"Dunarea de Jos" University of Galati (RO)
Affordable and clean energy
Openalex Percentile: Top 15%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.