Natural ventilation performance for airborne diseases management in a deployable treatment facility
OBJECTIVE: To assess whether wind-driven natural ventilation in the Infectious Diseases Treatment Module (IDTM) can achieve ventilation performance consistent with airborne precaution requirements [160 liters per second (L/s)] and to estimate associated pathogen-specific infection risks. METHODS: decays were conducted to validate the developed computational fluid dynamics (CFD) model. The validated CFD model simulated wind-driven natural ventilation (1-4 m/s) for an L-shaped IDTM configuration under four structural scenarios defined by the presence or absence of patient porches and mosquito nets. Airborne infection risk was estimated using a Wells-Riley quanta-based model for seven representative airborne pathogens under short-duration healthcare worker exposure and prolonged patient co-exposure. RESULTS: Ventilation performance varied widely based on wind speed and structural configuration. Airflow ranged from 7 L/s in the most restricted configuration (porch and mosquito nets present at 1 m/s) to over 3,100 L/s when mosquito nets were removed at 4 m/s.When mapped to infection-risk estimates, ventilation rates at 160 L/s substantially reduced short-duration healthcare worker infection risk for all pathogens (≤1%), whereas prolonged co-exposure remained associated with high risk for high-emission pathogens despite high ventilation. CONCLUSION: Under favorable wind conditions and optimized configurations, the IDTM can achieve ventilation rates consistent with the 160 L/s recommendation for airborne precautions. While this provides substantial protection for healthcare workers, individual-room isolation remains essential for patient management. Operationally, removing window-mounted nets is the most effective way to ensure safety targets are met; hybrid ventilation measures should be considered during low-wind conditions.
Authors
- Antoine Chaillon (ORCID: https://orcid.org/0000-0001-9490-3857)
- Michele Di Marco (ORCID: https://orcid.org/0009-0009-5407-7576)
- Anna Silenzi (ORCID: https://orcid.org/0000-0002-3893-8171)
- Robert Wunderlich (ORCID: https://orcid.org/0000-0002-2380-3581)
- Marco Dell’Isola (ORCID: https://orcid.org/0000-0001-8327-4354)
- Giorgio Buonanno (ORCID: https://orcid.org/0000-0003-0525-0781)
- G. Grossi (ORCID: https://orcid.org/0009-0001-2959-4936)
- Luca Fontana (ORCID: https://orcid.org/0000-0002-8614-4114)
Institutions
- World Health Organization - Pakistan (PK)
- Università degli studi di Cassino e del Lazio Meridionale (IT)
- University Children's Hospital Tübingen (DE)
Publication Details
- Journal
- Infection Control and Hospital Epidemiology
- Published
- 2026-07-16
- DOI
- https://doi.org/10.1017/ice.2026.10508
- Primary Topic
- Infection Control and Ventilation
- Type
- article
- Field-Weighted Citation Impact
- 0.00