Research on transformer temperature rise detection and optimization method based on multi-physical field coupling
To address the inefficiency of conventional temperature rise tests for dry-type transformers in box substations, this study proposes a closed-loop "Standard-Experiment-Simulation-Optimization" methodology. An electromagnetic‑thermal coupled model was built, calibrated with field test data. The simulation revealed a saturated exponential growth pattern of hotspot temperature rise, verified experimentally. Based on this, additional thermocouples were placed beyond standard positions, enabling earlier and more accurate hotspot measurement. A predictive model using the first‑five‑hour data was derived to estimate steady‑state temperature, rise value, and required test duration. This approach reduces testing time and provides a reusable reference for improving hotspot detection accuracy.
Authors
- Hongyun Zhao (ORCID: https://orcid.org/0000-0002-1251-3888)
- Shan Cheng (ORCID: https://orcid.org/0000-0002-8658-6916)
- Yu Zhang
Institutions
- General Administration of Quality Supervision, Inspection and Quarantine (CN)
- Xinjiang Uygur Autonomous Region Product Quality Supervision and Inspection Institute (CN)
- Changzhou Institute of Mechatronic Technology (CN)
Publication Details
- Journal
- Scientific Reports
- Published
- 2026-07-02
- DOI
- https://doi.org/10.1038/s41598-026-60800-7
- Primary Topic
- Power Transformer Diagnostics and Insulation
- Type
- article
- Field-Weighted Citation Impact
- 0.00