Experimental Analysis of MCCB Interruption Behavior Under Repetitive Overcurrent Conditions for Electrical Safety in Low-Voltage Distribution Systems

A molded case circuit breaker (MCCB) is a key protective device for electrical safety in low-voltage distribution systems, and its interruption performance is closely related to arc behavior during fault-current interruption. This study experimentally analyzed variations in the interruption behavior of MCCBs under repetitive overcurrent conditions with different current magnitudes. In this study, new repetitive interruption experiments were performed under the 7 kA condition, while the 2.8 kA results reported in our previous study were used for comparison. Four MCCB products with the same model and rated specifications are prepared and denoted as Products A–D. Repetitive interruption tests are performed under the same procedure, and the voltage waveform generated during interruption is divided into the total arcing time, arc extension period, and energy consumption period. The time and energy distributions of each period are then quantitatively compared. The results showed that, from the first to the third test, the average total arcing time increased by approximately 4.68%, while e the arc extension time and arc extension voltage-area-based index increased by approximately 15.98% and 19.47%, respectively. In contrast, the energy consumption time and energy consumption voltage-area-based index decreased by approximately 5.90% and 12.87%, respectively. Although the difference between the first and second tests is relatively large, the changes between the second and third tests are small, with the total arcing time and total arcing voltage-area-based index changing by only approximately −0.57% and −0.30%, respectively. These results indicate that variations in MCCB interruption behavior under repetitive overcurrent conditions are more sensitively reflected in the time and energy distribution between the arc extension and energy consumption periods than in the total arcing time alone. Therefore, voltage-waveform-based analysis of interrupting time and energy consumption ratio can be used to evaluate interruption behavior variations and potential performance degradation of MCCBs, supporting reliability assessment for electrical safety under repetitive fault conditions.

Authors

Institutions

Publication Details

Journal
Actuators
Published
2026-07-01
DOI
https://doi.org/10.3390/act15070361
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental Analysis of MCCB Interruption Behavior Under Repetitive Overcurrent Conditions for Electrical Safety in Low-Voltage Distribution Systems

Young-Maan Cho, Kun-A Lee, Houng-Kun Joung
Actuators
Electrical Fault Detection and Protection
article

Experimental Analysis of MCCB Interruption Behavior Under Repetitive Overcurrent Conditions for Electrical Safety in Low-Voltage Distribution Systems

Young-Maan Cho, Kun-A Lee, Houng-Kun Joung
article en

Abstract

A molded case circuit breaker (MCCB) is a key protective device for electrical safety in low-voltage distribution systems, and its interruption performance is closely related to arc behavior during fault-current interruption. This study experimentally analyzed variations in the interruption behavior of MCCBs under repetitive overcurrent conditions with different current magnitudes. In this study, new repetitive interruption experiments were performed under the 7 kA condition, while the 2.8 kA results reported in our previous study were used for comparison. Four MCCB products with the same model and rated specifications are prepared and denoted as Products A–D. Repetitive interruption tests are performed under the same procedure, and the voltage waveform generated during interruption is divided into the total arcing time, arc extension period, and energy consumption period. The time and energy distributions of each period are then quantitatively compared. The results showed that, from the first to the third test, the average total arcing time increased by approximately 4.68%, while e the arc extension time and arc extension voltage-area-based index increased by approximately 15.98% and 19.47%, respectively. In contrast, the energy consumption time and energy consumption voltage-area-based index decreased by approximately 5.90% and 12.87%, respectively. Although the difference between the first and second tests is relatively large, the changes between the second and third tests are small, with the total arcing time and total arcing voltage-area-based index changing by only approximately −0.57% and −0.30%, respectively. These results indicate that variations in MCCB interruption behavior under repetitive overcurrent conditions are more sensitively reflected in the time and energy distribution between the arc extension and energy consumption periods than in the total arcing time alone. Therefore, voltage-waveform-based analysis of interrupting time and energy consumption ratio can be used to evaluate interruption behavior variations and potential performance degradation of MCCBs, supporting reliability assessment for electrical safety under repetitive fault conditions.

ActuatorsVol. 15(7)
Inje University (KR), Hankyong National University (KR), Cheongju University (KR)
Korea Institute for Advancement of Technology, National Research Foundation of Korea
Affordable and clean energy
Openalex Percentile: Top 12%
Electrical Fault Detection and Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.