Effect of Different Collector Designs on Water Pressure Loss and Experimental Investigation of the Fan Coil Heat Exchanger

The aim of this study is to experimentally investigate the influence of collector design parameters on water-side pressure loss in fan coil heat exchangers. Pipe diameters (Ø16, Ø22, Ø25 mm), collector lengths (180 and 240 mm), and circuit numbers (2NC and 4NC) were evaluated through laboratory tests conducted on five different configurations over a flow range of 0.150–2.000 m³/h. The results show that for 2NC configurations, increasing pipe diameter led to a rise in pressure loss (ΔP), whereas in the 4NC configuration the same diameter increase resulted in a reduction in ΔP due to improved flow distribution. The 4NC design exhibited the lowest pressure losses, approximately one-third of those observed in comparable 2NC designs. Main-effect analysis revealed a clear sensitivity hierarchy among the investigated parameters: number of circuits (NC) >> diameter (D) > length (L). While the circuit number produced an average ΔP difference of approximately 35 kPa between 2NC and 4NC levels, the diameter effect remained within 1–3 kPa and the length effect below 1.5 kPa across the investigated range. The findings indicate that hydraulic performance in fan coil collectors is governed primarily by flow redistribution associated with circuit configuration rather than by simple geometric scaling of pipe diameter. These results provide quantitative support for optimizing collector design based on flow balance and cost-performance considerations.

Authors

Institutions

Publication Details

Journal
Düzce Üniversitesi Teknik Bilimler Dergisi
Published
2026-06-29
DOI
https://doi.org/10.70081/duted.1843844
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Effect of Different Collector Designs on Water Pressure Loss and Experimental Investigation of the Fan Coil Heat Exchanger

Hüseyin Pehlivan, Çiler Gizem Bostancı
Düzce Üniversitesi Teknik Bilimler Dergisi
Geothermal Energy Systems and Applications
article

Effect of Different Collector Designs on Water Pressure Loss and Experimental Investigation of the Fan Coil Heat Exchanger

Hüseyin Pehlivan, Çiler Gizem Bostancı
article en

Abstract

The aim of this study is to experimentally investigate the influence of collector design parameters on water-side pressure loss in fan coil heat exchangers. Pipe diameters (Ø16, Ø22, Ø25 mm), collector lengths (180 and 240 mm), and circuit numbers (2NC and 4NC) were evaluated through laboratory tests conducted on five different configurations over a flow range of 0.150–2.000 m³/h. The results show that for 2NC configurations, increasing pipe diameter led to a rise in pressure loss (ΔP), whereas in the 4NC configuration the same diameter increase resulted in a reduction in ΔP due to improved flow distribution. The 4NC design exhibited the lowest pressure losses, approximately one-third of those observed in comparable 2NC designs. Main-effect analysis revealed a clear sensitivity hierarchy among the investigated parameters: number of circuits (NC) >> diameter (D) > length (L). While the circuit number produced an average ΔP difference of approximately 35 kPa between 2NC and 4NC levels, the diameter effect remained within 1–3 kPa and the length effect below 1.5 kPa across the investigated range. The findings indicate that hydraulic performance in fan coil collectors is governed primarily by flow redistribution associated with circuit configuration rather than by simple geometric scaling of pipe diameter. These results provide quantitative support for optimizing collector design based on flow balance and cost-performance considerations.

Düzce Üniversitesi Teknik Bilimler DergisiVol. 4(1)
Sakarya University (TR), Institute of Natural Science (KP)
Clean water and sanitation
Openalex Percentile: Top 20%
Geothermal Energy Systems and Applications
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Effect of Different Collector Designs on Water Pressure Loss and Experimental Investigation of the Fan Coil Heat Exchanger — Hüseyin Pehlivan, Çiler Gizem Bostancı · Düzce Üniversitesi Teknik Bilimler Dergisi (2026) | TGRS Research Map | TGRS