BRICK-Automated Virtual Temperature Sensors for Sensor Fault Detection, Isolation, and Discrimination in Smart-Building HVAC Systems

Sensor bias faults in closed-loop HVAC systems pose a detection challenge that is both subtle and costly. Because the control loop compensates for biased readings by driving the affected sensor back toward its setpoint, the fault becomes invisible to conventional threshold monitors. The anomaly does not vanish, however; it is redistributed across correlated sensors, disrupting their mutual consistency. We propose a framework that automatically derives virtual temperature sensor models from BRICK schema metadata. LightGBM regressors, trained on fault-free inter-sensor relationships, produce z-scored prediction residuals that serve as detection signals. Fault isolation is achieved by ranking sensors by their median daily anomaly scores; fault-type discrimination relies on analysis of actuator command-position discrepancies. On the Lawrence Berkeley National Laboratory (LBNL) fault detection and diagnosis (FDD) benchmark, the method achieves an area under the receiver operating characteristic curve (AUC) of 0.9992 for the mildest sensor bias (SA +2∘C), an AUC of 1.0 for all other single-duct air handling unit (SD-AHU) scenarios, and an AUC of 1.0 for all fan coil unit (FCU) sensor bias scenarios. In all four SD-AHU sensor bias scenarios, the biased sensor (SA_TEMP) ranks first or second; for the larger biases (±4∘C), SA_TEMP consistently ranks first. A robustness analysis over 10 random seeds confirms that detection AUC remains above 0.997 in all cases. Sensor and mechanical faults fall into non-overlapping clusters in the command-position discrepancy space. On the FCU system, the proposed method substantially outperforms principal component analysis (PCA) (AUC = 1.0 versus 0.63–0.90) and provides diagnostic capabilities not available with PCA. Notably, a single pipeline function handles both system types without modification, confirming cross-system scalability through the BRICK metadata layer. The results confirm that BRICK-automated virtual sensor construction is a viable approach for scalable, deployment-ready sensor validation in smart-building HVAC systems.

Authors

Institutions

Publication Details

Journal
Sensors
Published
2026-05-31
DOI
https://doi.org/10.3390/s26113465
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

BRICK-Automated Virtual Temperature Sensors for Sensor Fault Detection, Isolation, and Discrimination in Smart-Building HVAC Systems

Khaled Chahine, Hassan N. Noura
Sensors
Building Energy and Comfort Optimization
article

BRICK-Automated Virtual Temperature Sensors for Sensor Fault Detection, Isolation, and Discrimination in Smart-Building HVAC Systems

Khaled Chahine, Hassan N. Noura
article en

Abstract

Sensor bias faults in closed-loop HVAC systems pose a detection challenge that is both subtle and costly. Because the control loop compensates for biased readings by driving the affected sensor back toward its setpoint, the fault becomes invisible to conventional threshold monitors. The anomaly does not vanish, however; it is redistributed across correlated sensors, disrupting their mutual consistency. We propose a framework that automatically derives virtual temperature sensor models from BRICK schema metadata. LightGBM regressors, trained on fault-free inter-sensor relationships, produce z-scored prediction residuals that serve as detection signals. Fault isolation is achieved by ranking sensors by their median daily anomaly scores; fault-type discrimination relies on analysis of actuator command-position discrepancies. On the Lawrence Berkeley National Laboratory (LBNL) fault detection and diagnosis (FDD) benchmark, the method achieves an area under the receiver operating characteristic curve (AUC) of 0.9992 for the mildest sensor bias (SA +2∘C), an AUC of 1.0 for all other single-duct air handling unit (SD-AHU) scenarios, and an AUC of 1.0 for all fan coil unit (FCU) sensor bias scenarios. In all four SD-AHU sensor bias scenarios, the biased sensor (SA_TEMP) ranks first or second; for the larger biases (±4∘C), SA_TEMP consistently ranks first. A robustness analysis over 10 random seeds confirms that detection AUC remains above 0.997 in all cases. Sensor and mechanical faults fall into non-overlapping clusters in the command-position discrepancy space. On the FCU system, the proposed method substantially outperforms principal component analysis (PCA) (AUC = 1.0 versus 0.63–0.90) and provides diagnostic capabilities not available with PCA. Notably, a single pipeline function handles both system types without modification, confirming cross-system scalability through the BRICK metadata layer. The results confirm that BRICK-automated virtual sensor construction is a viable approach for scalable, deployment-ready sensor validation in smart-building HVAC systems.

SensorsVol. 26(11)
Centre National de la Recherche Scientifique (FR), Franche-Comté Électronique Mécanique Thermique et Optique - Sciences et Technologies (FR), American University of the Middle East (KW), Université Marie et Louis Pasteur (FR), American University of Beirut (LB)
Reduced inequalities
Openalex Percentile: Top 7%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.