Changes in the characteristics of the insulating materials that compose the Capacitor Voltage Transformers (CVT) or insulation abnormalities in the oil-impregnated paper capacitors in the CVT are manifested as changes in the CVT transformation ratio. In this paper, a diagnostic method based on the measurement of CVT secondary voltage was investigated. The change in the CVT secondary voltage (calculated value) in the event of a single element breakdown of oil-impregnated paper capacitors is sufficiently large compared to the dispersion in the secondary voltage (measured value) of actual CVTs used in the substation. It was shown that CVT diagnosis is possible by comparing the secondary voltages of CVTs connected to the same bus bar in the substation with each other. A concrete example of the CVT diagnosis flow when applied to an actual substation is also presented.

Authors

Institutions

Publication Details

Journal
IEEJ Transactions on Power and Energy
Published
2026-05-31
DOI
https://doi.org/10.1541/ieejpes.146.434
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Consideration of Condition Monitoring Methods for Capacitor Voltage Transformers

Yuya Nagaki, H. Kojima, Naoki Hayakawa, Masanobu Yoshida et al.
IEEJ Transactions on Power and Energy
Electrical Fault Detection and Protection
article

Consideration of Condition Monitoring Methods for Capacitor Voltage Transformers

Yuya Nagaki, H. Kojima, Naoki Hayakawa, Masanobu Yoshida, Hiroko Isaji
article en

Abstract

Changes in the characteristics of the insulating materials that compose the Capacitor Voltage Transformers (CVT) or insulation abnormalities in the oil-impregnated paper capacitors in the CVT are manifested as changes in the CVT transformation ratio. In this paper, a diagnostic method based on the measurement of CVT secondary voltage was investigated. The change in the CVT secondary voltage (calculated value) in the event of a single element breakdown of oil-impregnated paper capacitors is sufficiently large compared to the dispersion in the secondary voltage (measured value) of actual CVTs used in the substation. It was shown that CVT diagnosis is possible by comparing the secondary voltages of CVTs connected to the same bus bar in the substation with each other. A concrete example of the CVT diagnosis flow when applied to an actual substation is also presented.

IEEJ Transactions on Power and EnergyVol. 146(6)
Nagoya University (JP), Chubu Electric Power (Japan) (JP)
Affordable and clean energy
Openalex Percentile: Top 9%
Electrical Fault Detection and Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.