The electrical connection structure of the grid-side bushing of a converter transformer is a core current-carrying component in ultra-high voltage direct current (UHVDC) transmission systems. Under seismic conditions, it is prone to overheating and discharge faults, endangering the safe operation of converter stations. To reveal the damage mechanism and temperature evolution law of the electrical connection structure under seismic conditions, this paper establishes a refined finite element model for the structure and conducts seismic response analysis. Combined with the empirical formula of contact resistance and the electrothermal coupling model, the evolution of contact resistance and distribution characteristics of the temperature field of the electrical connection structure under different seismic peak accelerations are analyzed. The results indicate that earthquakes disrupt the stress distribution at the electrical contact interface, causing eccentric load and stress concentration, reducing the effective high-stress current-carrying area. The contact resistance rises rapidly with increasing acceleration, leading to severe degradation of current-carrying performance. The increase in contact resistance results in a manifold increase of Joule heat, and both the maximum and minimum temperatures of the structure increase significantly as acceleration rises. This study clarifies the mechanical–electrothermal coupling response mechanism of the structure, providing theoretical basis and technical support for its seismic design, thermal stability evaluation, operation, maintenance, and overhaul.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-05-28
DOI
https://doi.org/10.3390/en19112617
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Simulation and Evolution Analysis of Temperature Field of Electrical Connection Structure for Grid-Side Bushing of Converter Transformer Under Seismic Conditions

Yuhan Zou, Shoulong Dong, Chenguo Yao, Yi Liu et al.
Energies
HVDC Systems and Fault Protection
article

Simulation and Evolution Analysis of Temperature Field of Electrical Connection Structure for Grid-Side Bushing of Converter Transformer Under Seismic Conditions

Yuhan Zou, Shoulong Dong, Chenguo Yao, Yi Liu, Guannan Li, Zongxia Shi, Fan Liu, Songhai Fan, Haokun Yang, Xianghang Bu
article en

Abstract

The electrical connection structure of the grid-side bushing of a converter transformer is a core current-carrying component in ultra-high voltage direct current (UHVDC) transmission systems. Under seismic conditions, it is prone to overheating and discharge faults, endangering the safe operation of converter stations. To reveal the damage mechanism and temperature evolution law of the electrical connection structure under seismic conditions, this paper establishes a refined finite element model for the structure and conducts seismic response analysis. Combined with the empirical formula of contact resistance and the electrothermal coupling model, the evolution of contact resistance and distribution characteristics of the temperature field of the electrical connection structure under different seismic peak accelerations are analyzed. The results indicate that earthquakes disrupt the stress distribution at the electrical contact interface, causing eccentric load and stress concentration, reducing the effective high-stress current-carrying area. The contact resistance rises rapidly with increasing acceleration, leading to severe degradation of current-carrying performance. The increase in contact resistance results in a manifold increase of Joule heat, and both the maximum and minimum temperatures of the structure increase significantly as acceleration rises. This study clarifies the mechanical–electrothermal coupling response mechanism of the structure, providing theoretical basis and technical support for its seismic design, thermal stability evaluation, operation, maintenance, and overhaul.

EnergiesVol. 19(11)
Chongqing University (CN)
Openalex Percentile: Top 8%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.