Multi-Physical Coupling Collaborative Control Mechanism for 550 kV High-Speed Circuit Breaker

This investigation examines the decline in breaking performance observed in 550 kV high-speed circuit breakers, tracing the cause to insufficient coordination between the operating mechanism and the arc-extinguishing chamber. It proposes a coordinated adjustment of the buffer strategy mechanism and the structural parameters of the arc-extinguishing chamber, revealing their interaction under high-speed opening conditions. To address the impact loads and unstable airflow field during the mechanism’s high-speed opening, the buffer strategy was revised by increasing the gaps in the first four steps by 0.3 mm and 0.5 mm in two respective optimization schemes. Set the step size to 3 mm, and assign a decrease of zero for each of the final three steps. A 1 mm gap reduces the pressure drop near the end of the opening phase. The axial airflow velocity and the breaking performance were compared at the moment of 1 ms before current zero for three nozzle throat lengths (Lu): 22 mm, 27 mm, and 32 mm. Nozzle throat length has a clear effect on the main parameters of short-arc quenching. With a 27 mm throat length, the measured values remain relatively high. The proposed length scheme achieves a balanced trade-off between the airflow velocity distribution and the efficiency of arc cooling. Downstream of the nozzle, the axial airflow velocity is 18% higher than in the 32 mm scheme, and the pressure decays 22% more slowly than in the 22 mm scheme. This improves heat removal from the arc and shortens the short-arc phase to under 6 ms. Prototype tests provided by the manufacturer indicate that the circuit breaker with a 27 mm nozzle throat can achieve a minimum arcing time of approximately 6 ms, which is consistent with the simulation prediction.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-05-22
DOI
https://doi.org/10.3390/en19112502
Primary Topic
Vacuum and Plasma Arcs
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Multi-Physical Coupling Collaborative Control Mechanism for 550 kV High-Speed Circuit Breaker

Qijie Zhu, Bowen Xu, Jianwei Wei, Jianlei Zhao et al.
Energies
Vacuum and Plasma Arcs
article

Multi-Physical Coupling Collaborative Control Mechanism for 550 kV High-Speed Circuit Breaker

Qijie Zhu, Bowen Xu, Jianwei Wei, Jianlei Zhao, Enyang Xing, Shaoan Wang, Tianbo Zhang, Qingchao Sun, Lumin Zhao
article en

Abstract

This investigation examines the decline in breaking performance observed in 550 kV high-speed circuit breakers, tracing the cause to insufficient coordination between the operating mechanism and the arc-extinguishing chamber. It proposes a coordinated adjustment of the buffer strategy mechanism and the structural parameters of the arc-extinguishing chamber, revealing their interaction under high-speed opening conditions. To address the impact loads and unstable airflow field during the mechanism’s high-speed opening, the buffer strategy was revised by increasing the gaps in the first four steps by 0.3 mm and 0.5 mm in two respective optimization schemes. Set the step size to 3 mm, and assign a decrease of zero for each of the final three steps. A 1 mm gap reduces the pressure drop near the end of the opening phase. The axial airflow velocity and the breaking performance were compared at the moment of 1 ms before current zero for three nozzle throat lengths (Lu): 22 mm, 27 mm, and 32 mm. Nozzle throat length has a clear effect on the main parameters of short-arc quenching. With a 27 mm throat length, the measured values remain relatively high. The proposed length scheme achieves a balanced trade-off between the airflow velocity distribution and the efficiency of arc cooling. Downstream of the nozzle, the axial airflow velocity is 18% higher than in the 32 mm scheme, and the pressure decays 22% more slowly than in the 22 mm scheme. This improves heat removal from the arc and shortens the short-arc phase to under 6 ms. Prototype tests provided by the manufacturer indicate that the circuit breaker with a 27 mm nozzle throat can achieve a minimum arcing time of approximately 6 ms, which is consistent with the simulation prediction.

EnergiesVol. 19(11)
Electric Power Research Institute (US), Pingdingshan University (CN), Shenyang University of Technology (CN), State Grid Corporation of China (China) (CN), Shanghai Electric (China) (CN), Xi’an Jiaotong-Liverpool University (CN)
Affordable and clean energy
Openalex Percentile: Top 5%
Vacuum and Plasma Arcs
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.