Uncertainty-aware temperature field reconstruction from sparse samples and sensing via latent-space enhancement for GIS digital twin applications

Efficient and reliable full-state temperature estimation is critical for condition monitoring and digital twin applications of enclosed high-voltage equipment, yet it remains challenging due to sparse measurements and the high computational cost of multiphysics simulations. This paper proposes an uncertainty-aware workflow for full-state temperature estimation of a 550 kV gas-insulated switchgear (GIS) disconnector under contact degradation scenarios, based on a proper orthogonal decomposition (POD) reduced-order representation. A probabilistic forward surrogate enables posterior-driven data augmentation, while a lightweight inverse surrogate is trained to infer POD coefficients from only three temperature measurements on the enclosure surface, followed by full-state reconstruction with uncertainty quantification. Numerical results on the evaluated cases show favorable reconstruction accuracy and noise tolerance, with lower errors than gappy POD under the reported settings despite using fewer sensors. These results indicate the potential of the proposed workflow for digital twin-oriented temperature-field estimation in GIS.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2026-05-13
DOI
https://doi.org/10.1038/s41598-026-52842-8
Primary Topic
Thermal Analysis in Power Transmission
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Uncertainty-aware temperature field reconstruction from sparse samples and sensing via latent-space enhancement for GIS digital twin applications

Jiangang Ding, Zaixing Peng, Shaoshuai Su, Yi-Xiang Wang et al.
Scientific Reports
Thermal Analysis in Power Transmission
article

Uncertainty-aware temperature field reconstruction from sparse samples and sensing via latent-space enhancement for GIS digital twin applications

Jiangang Ding, Zaixing Peng, Shaoshuai Su, Yi-Xiang Wang, Wenchuan Chen, Wensheng Gao, Ziqi Zhou, Bo Liu
article en

Abstract

Efficient and reliable full-state temperature estimation is critical for condition monitoring and digital twin applications of enclosed high-voltage equipment, yet it remains challenging due to sparse measurements and the high computational cost of multiphysics simulations. This paper proposes an uncertainty-aware workflow for full-state temperature estimation of a 550 kV gas-insulated switchgear (GIS) disconnector under contact degradation scenarios, based on a proper orthogonal decomposition (POD) reduced-order representation. A probabilistic forward surrogate enables posterior-driven data augmentation, while a lightweight inverse surrogate is trained to infer POD coefficients from only three temperature measurements on the enclosure surface, followed by full-state reconstruction with uncertainty quantification. Numerical results on the evaluated cases show favorable reconstruction accuracy and noise tolerance, with lower errors than gappy POD under the reported settings despite using fewer sensors. These results indicate the potential of the proposed workflow for digital twin-oriented temperature-field estimation in GIS.

Scientific Reports
China Southern Power Grid (China) (CN), Switch (CH), Tsinghua University (CN)
China Southern Power Grid
Openalex Percentile: Top 7%
Thermal Analysis in Power Transmission
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.