Thermodynamic and Property‐Driven Evaluation of Low‐GWP Refrigerants as Alternatives to R‐134a in VCR Systems

ABSTRACT The global phase‐out of high‐global warming potential (high‐GWP) refrigerants has intensified the search for environmentally benign and energy‐efficient alternatives to R‐134a in vapor compression refrigeration systems (VCRS). This study presents a comprehensive thermodynamic evaluation of low‐GWP refrigerants, including R‐152a, R‐515B, R‐1234ze(E), R‐1234yf, R‐290, R‐600a, R‐600, and R‐1270, as potential replacements for R‐134a. A steady‐state thermodynamic cycle model was developed, incorporating fixed superheating and subcooling levels, with simulations conducted for evaporator temperatures between −10°C and 15°C and condenser temperatures between 10°C and 50°C. Key performance indicators such as coefficient of performance (COP), compressor power consumption, and refrigerant mass‐flow rate were calculated and normalized relative to R‐134a. The results show that hydrocarbon refrigerants (R‐600a and R‐600) achieve up to 3%–4% higher COP than R‐134a, while R‐152a provides approximately 3%–4% COP improvement with reduced compressor power (~ 4%). In contrast, R‐1234yf exhibits 4%–5% lower COP and 2%–5% higher compressor power, whereas R‐290 and R‐1270 show moderate efficiency penalties of 1%–3%. R‐515B and R‐1234ze(E) demonstrate near‐baseline performance, with COP variations within ±1% of R‐134a. Mass‐flow rate reductions of 40%–50% are observed for hydrocarbons and R‐152a due to higher latent heat, while R‐1234yf requires 25%–28% higher flow rate. The results further reveal that performance trends are strongly governed by latent heat, thermal conductivity, viscosity, and reduced pressure. Overall, low‐GWP refrigerants can deliver comparable or superior thermodynamic performance to R‐134a, though trade‐offs between efficiency, compressor loading, and volumetric capacity must be considered. These findings provide practical guidance for selecting sustainable refrigerants that balance environmental impact and operational efficiency in future cooling system design.

Authors

Institutions

Publication Details

Journal
Heat Transfer
Published
2026-05-11
DOI
https://doi.org/10.1002/htj.70274
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Thermodynamic and Property‐Driven Evaluation of Low‐GWP Refrigerants as Alternatives to R‐134a in VCR Systems

Abhishek Kumar, S.I. Yang, Chi‐Chuan Wang
Heat Transfer
Refrigeration and Air Conditioning Technologies
article

Thermodynamic and Property‐Driven Evaluation of Low‐GWP Refrigerants as Alternatives to R‐134a in VCR Systems

Abhishek Kumar, S.I. Yang, Chi‐Chuan Wang
article en

Abstract

ABSTRACT The global phase‐out of high‐global warming potential (high‐GWP) refrigerants has intensified the search for environmentally benign and energy‐efficient alternatives to R‐134a in vapor compression refrigeration systems (VCRS). This study presents a comprehensive thermodynamic evaluation of low‐GWP refrigerants, including R‐152a, R‐515B, R‐1234ze(E), R‐1234yf, R‐290, R‐600a, R‐600, and R‐1270, as potential replacements for R‐134a. A steady‐state thermodynamic cycle model was developed, incorporating fixed superheating and subcooling levels, with simulations conducted for evaporator temperatures between −10°C and 15°C and condenser temperatures between 10°C and 50°C. Key performance indicators such as coefficient of performance (COP), compressor power consumption, and refrigerant mass‐flow rate were calculated and normalized relative to R‐134a. The results show that hydrocarbon refrigerants (R‐600a and R‐600) achieve up to 3%–4% higher COP than R‐134a, while R‐152a provides approximately 3%–4% COP improvement with reduced compressor power (~ 4%). In contrast, R‐1234yf exhibits 4%–5% lower COP and 2%–5% higher compressor power, whereas R‐290 and R‐1270 show moderate efficiency penalties of 1%–3%. R‐515B and R‐1234ze(E) demonstrate near‐baseline performance, with COP variations within ±1% of R‐134a. Mass‐flow rate reductions of 40%–50% are observed for hydrocarbons and R‐152a due to higher latent heat, while R‐1234yf requires 25%–28% higher flow rate. The results further reveal that performance trends are strongly governed by latent heat, thermal conductivity, viscosity, and reduced pressure. Overall, low‐GWP refrigerants can deliver comparable or superior thermodynamic performance to R‐134a, though trade‐offs between efficiency, compressor loading, and volumetric capacity must be considered. These findings provide practical guidance for selecting sustainable refrigerants that balance environmental impact and operational efficiency in future cooling system design.

Heat Transfer
National Yang Ming Chiao Tung University (TW), National Formosa University (TW)
Openalex Percentile: Top 8%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.