Novel fault area identification scheme for VSC-HVDC grids based on traveling-wave dispersion coefficient
Compared with the distributed configuration of current-limiting reactors at both line terminals, centralized installation of reactors at converter station outlets in VSC-based DC grids allows not only reduced construction costs but also enhanced economic efficiency. To address the incompatibility of boundary-based single-ended protection schemes with this topology, this paper derives analytical expressions for line-mode voltage traveling-wave during internal and external faults based on traveling-wave dispersion phenomena. The results demonstrate that both fault types exhibit double-exponential decay characteristics, with the dispersion coefficient-related exponential term for internal faults exceeding that of external faults. A protection scheme is subsequently developed by extracting this coefficient through the Levenberg-Marquardt (LM) algorithm. PSCAD/EMTDC simulations confirm that the proposed scheme covers the majority of line sections and exhibits robust tolerance to transition al resistances.
Authors
- Wei Dong (ORCID: https://orcid.org/0000-0003-0263-3584)
- Lijian Jiang (ORCID: https://orcid.org/0000-0002-3410-1219)
- Lixuan Zhu
- Zelai Sun
- Biao Li
- Fei Yang
- Lin Zheng
- Dawei Chen
Institutions
- State Grid Corporation of China (China) (CN)
- Fujian Electric Power Survey & Design Institute (CN)
- State Nuclear Power Technology Company (China) (CN)
Publication Details
- Journal
- IET conference proceedings.
- Published
- 2026-05-01
- DOI
- https://doi.org/10.1049/icp.2026.0651
- Primary Topic
- HVDC Systems and Fault Protection
- Type
- article
- Field-Weighted Citation Impact
- 0.00