Exploring Energy Use Intensity Correlations in England’s NHS Acute Hospitals: Structural and Decarbonization Patterns (2018–2025)

Analysis of Estates Return Information Collection (ERIC) 2018/19–2024/25 data for 1104 acute NHS hospital sites in England found persistently high energy use intensity (EUI), averaging 211 kWh/m2 in 2024/25, with total acute-sector energy use of 9.99 billion kWh, with approximately 75% derived from gas. Longitudinal trends indicated relatively stable EUI despite portfolio growth. Cross-sectional exploratory analyses for 2024/25 showed that clinical floor area share (mean 59%) exhibited the strongest observed association with EUI (r = 0.52, R2 = 0.27), followed by gross internal area (r = 0.39, R2 = 0.15) and backlog intensity (r = 0.23). Associations between building age cohorts and EUI were generally weak or negligible, except for a weak positive association for 1985–94 buildings (r = 0.064) and a moderate negative association for 2005–14 buildings (r = −0.126). Among the decarbonization and operational indicators examined, renewable electricity fraction showed the strongest bivariate association with EUI (R2 = 0.224), followed by water intensity (R2 = 0.101), gas share (R2 = 0.085), LED coverage (R2 = 0.027), climate incidents (R2 = 0.020), and waste intensity (R2 = 0.004). Sites with heat decarbonization plans, high LED coverage, or heat pump installations tended to exhibit higher EUI values alongside differing renewable electricity uptake patterns, potentially reflecting the prioritization of interventions at more energy-intensive facilities. Overall, the findings suggest that hospital energy intensity is associated with functional mix, estate characteristics, and decarbonization-related indicators, although these relationships should be interpreted as exploratory associations rather than independent causal effects. The study provides a national-scale exploratory benchmarking assessment intended to inform future multivariable and longitudinal research on NHS estate decarbonization strategies.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2026-04-29
DOI
https://doi.org/10.3390/buildings16091782
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Exploring Energy Use Intensity Correlations in England’s NHS Acute Hospitals: Structural and Decarbonization Patterns (2018–2025)

Anosh Nadeem Butt
Buildings
Building Energy and Comfort Optimization
article

Exploring Energy Use Intensity Correlations in England’s NHS Acute Hospitals: Structural and Decarbonization Patterns (2018–2025)

Anosh Nadeem Butt
article en

Abstract

Analysis of Estates Return Information Collection (ERIC) 2018/19–2024/25 data for 1104 acute NHS hospital sites in England found persistently high energy use intensity (EUI), averaging 211 kWh/m2 in 2024/25, with total acute-sector energy use of 9.99 billion kWh, with approximately 75% derived from gas. Longitudinal trends indicated relatively stable EUI despite portfolio growth. Cross-sectional exploratory analyses for 2024/25 showed that clinical floor area share (mean 59%) exhibited the strongest observed association with EUI (r = 0.52, R2 = 0.27), followed by gross internal area (r = 0.39, R2 = 0.15) and backlog intensity (r = 0.23). Associations between building age cohorts and EUI were generally weak or negligible, except for a weak positive association for 1985–94 buildings (r = 0.064) and a moderate negative association for 2005–14 buildings (r = −0.126). Among the decarbonization and operational indicators examined, renewable electricity fraction showed the strongest bivariate association with EUI (R2 = 0.224), followed by water intensity (R2 = 0.101), gas share (R2 = 0.085), LED coverage (R2 = 0.027), climate incidents (R2 = 0.020), and waste intensity (R2 = 0.004). Sites with heat decarbonization plans, high LED coverage, or heat pump installations tended to exhibit higher EUI values alongside differing renewable electricity uptake patterns, potentially reflecting the prioritization of interventions at more energy-intensive facilities. Overall, the findings suggest that hospital energy intensity is associated with functional mix, estate characteristics, and decarbonization-related indicators, although these relationships should be interpreted as exploratory associations rather than independent causal effects. The study provides a national-scale exploratory benchmarking assessment intended to inform future multivariable and longitudinal research on NHS estate decarbonization strategies.

BuildingsVol. 16(9)
University of Glasgow (GB), City of Glasgow College (GB)
Climate action
Openalex Percentile: Top 11%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.