Fire behaviour of twisted pair communication cables

• Thermal and elemental analysis of PVC, PE, LSZH and LSZHFR cable sheaths was performed. • FTIR confirmed HCl release in PVC even at low decomposition temperatures. • Firefighting wastewater from PVC showed the highest toxicity to Vibrio fischeri. • LSZHFR cables exhibited the lowest ecotoxicity and superior fire safety. • All tested cable runoff samples were classified as hazardous property HP14. Unshielded twisted pair (UTP) cables are ubiquitous in modern building infrastructures; however, the multifaceted risks associated with their combustion remain insufficiently addressed. This study provides a comprehensive assessment of Category 6 UTP cables (PE, PVC, LSZH, and LSZHFR) using cone calorimetry, FTIR spectroscopy, and ecotoxicological bioassays. Calorimetric results revealed significant differences in fire load, with Total Heat Release (THR) values ranging from 123.95 MJ·m⁻² for PE to 76.58 MJ·m⁻² for LSZH cables. The environmental impact was quantified through ecotoxicity assays of simulated firefighting wastewater. Bioassays using Vibrio fischeri demonstrated high toxicity across all samples, with PVC cables exhibiting the most severe impact (EC₅₀ of 29.51 mL·L⁻¹ after 30 minutes). In contrast, assays with white mustard ( Sinapis alba ) showed no significant inhibition; instead, hyperstimulation (up to 81.93% for PE) was observed at high concentrations, suggesting a high inherent resistance of seeds to firefighting wastewater contaminants. Based on the bacterial response, all tested cable runoff met the criteria for the hazardous property HP14 (Ecotoxic) according to Decree No. 8/2021 Coll. These findings underscore that UTP cable fires pose a dual threat: substantial thermal release and critical aquatic toxicity, necessitating the integration of ecotoxicological metrics into building fire safety standards.

Authors

Institutions

Publication Details

Journal
Applications in Energy and Combustion Science
Published
2026-04-28
DOI
https://doi.org/10.1016/j.jaecs.2026.100505
Primary Topic
Fire dynamics and safety research
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Fire behaviour of twisted pair communication cables

Dana Chudová, Milan Dej, Jan Slaný, Petra Roupcová et al.
Applications in Energy and Combustion Science
Fire dynamics and safety research
article

Fire behaviour of twisted pair communication cables

Dana Chudová, Milan Dej, Jan Slaný, Petra Roupcová, Aleš Dudáček, Vojtěch Pelech, Izabela Šudrychová
article en

Abstract

• Thermal and elemental analysis of PVC, PE, LSZH and LSZHFR cable sheaths was performed. • FTIR confirmed HCl release in PVC even at low decomposition temperatures. • Firefighting wastewater from PVC showed the highest toxicity to Vibrio fischeri. • LSZHFR cables exhibited the lowest ecotoxicity and superior fire safety. • All tested cable runoff samples were classified as hazardous property HP14. Unshielded twisted pair (UTP) cables are ubiquitous in modern building infrastructures; however, the multifaceted risks associated with their combustion remain insufficiently addressed. This study provides a comprehensive assessment of Category 6 UTP cables (PE, PVC, LSZH, and LSZHFR) using cone calorimetry, FTIR spectroscopy, and ecotoxicological bioassays. Calorimetric results revealed significant differences in fire load, with Total Heat Release (THR) values ranging from 123.95 MJ·m⁻² for PE to 76.58 MJ·m⁻² for LSZH cables. The environmental impact was quantified through ecotoxicity assays of simulated firefighting wastewater. Bioassays using Vibrio fischeri demonstrated high toxicity across all samples, with PVC cables exhibiting the most severe impact (EC₅₀ of 29.51 mL·L⁻¹ after 30 minutes). In contrast, assays with white mustard ( Sinapis alba ) showed no significant inhibition; instead, hyperstimulation (up to 81.93% for PE) was observed at high concentrations, suggesting a high inherent resistance of seeds to firefighting wastewater contaminants. Based on the bacterial response, all tested cable runoff met the criteria for the hazardous property HP14 (Ecotoxic) according to Decree No. 8/2021 Coll. These findings underscore that UTP cable fires pose a dual threat: substantial thermal release and critical aquatic toxicity, necessitating the integration of ecotoxicological metrics into building fire safety standards.

Applications in Energy and Combustion ScienceVol. 26
VSB - Technical University of Ostrava (CZ)
Openalex Percentile: Top 11%
Fire dynamics and safety research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.