Thermal Design and Performance Modeling of A High Compute Density Liquid Cooled Chiller Less Modular Edge Data Center

Abstract Holistic design of a modular energy-efficient edge datacenter with compute densities of 20 kW/m3 is presented. The datacenter uses a single chiller-less liquid loop to extract heat from server components and reject it to the ambient using a mixture of 25% propylene glycol and water. Heat is extracted from the chips using a micro-pin array cold plate and rejected to the ambient air is achieved using a counter-flow microchannel polymer heat exchanger (MPHX) dry cooler. Experiments on performance of the cold plate and MPHX components are presented, and a validated system model of the cooling loop is developed. Baseline performance results at an outdoor temperature of 40 C for a maximum GPU case temperature of 75 C reveals an optimum setting of liquid flow rate and dry cooler fan flow rate to minimize the system cooling power to under 4 percent of the compute power. Sensitivity studies are performed to assess the impact of improvements in thermal interface material, cold plate convective resistance, and dry cooler air-side heat transfer coefficient on system performance. Results show that a combination of improvements to the cold plate and dry cooler, or a significant reduction in TIM resistance can decrease the cooling power ratio. Annual simulations in Portland, Sacramento, and Phoenix show that the edge datacenter uses 1.34, 1.32 and 1.7% of the compute electrical energy for cooling, respectively, with peak ratio under 5 percent for 98.42% of the hours in the hottest location.

Authors

Institutions

Publication Details

Journal
Journal of Electronic Packaging
Published
2026-04-27
DOI
https://doi.org/10.1115/1.4071752
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Thermal Design and Performance Modeling of A High Compute Density Liquid Cooled Chiller Less Modular Edge Data Center

Erfan Rasouli, Ines-Noelly Tano, Vinod Narayanan
Journal of Electronic Packaging
Heat Transfer and Optimization
article

Thermal Design and Performance Modeling of A High Compute Density Liquid Cooled Chiller Less Modular Edge Data Center

Erfan Rasouli, Ines-Noelly Tano, Vinod Narayanan
article en

Abstract

Abstract Holistic design of a modular energy-efficient edge datacenter with compute densities of 20 kW/m3 is presented. The datacenter uses a single chiller-less liquid loop to extract heat from server components and reject it to the ambient using a mixture of 25% propylene glycol and water. Heat is extracted from the chips using a micro-pin array cold plate and rejected to the ambient air is achieved using a counter-flow microchannel polymer heat exchanger (MPHX) dry cooler. Experiments on performance of the cold plate and MPHX components are presented, and a validated system model of the cooling loop is developed. Baseline performance results at an outdoor temperature of 40 C for a maximum GPU case temperature of 75 C reveals an optimum setting of liquid flow rate and dry cooler fan flow rate to minimize the system cooling power to under 4 percent of the compute power. Sensitivity studies are performed to assess the impact of improvements in thermal interface material, cold plate convective resistance, and dry cooler air-side heat transfer coefficient on system performance. Results show that a combination of improvements to the cold plate and dry cooler, or a significant reduction in TIM resistance can decrease the cooling power ratio. Annual simulations in Portland, Sacramento, and Phoenix show that the edge datacenter uses 1.34, 1.32 and 1.7% of the compute electrical energy for cooling, respectively, with peak ratio under 5 percent for 98.42% of the hours in the hottest location.

Journal of Electronic Packaging
Department of Aerospace Science and Technology (BR), University of California, Davis (US), Central Arizona College (US)
Affordable and clean energy
Openalex Percentile: Top 7%
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.