Suppression of corrosion-driven hydrogen generation in gas turbine closed cooling water systems through transition from ammonium hydroxide–carbohydrazide to a nitrite-based inhibitor program

Reliable operation of closed cooling-water circuits in gas-turbine combined-cycle plants depends on appropriate cycle-chemistry design, monitoring, and control. This case study documents an engineered transition in the Gas Turbine Closed Circuit Cooling Water (GT-CCCW) system of a 414 MW combined-cycle power plant to eliminate corrosion-driven hydrogen (H 2 ) formation and stabilize operation, following the detection of significant hydrogen accumulation in the closed circuit, where gas-phase hydrogen concentrations measured after extraction reached an equivalent value of 16,035 mg L -1 (1.6%). Leak investigations confirmed no hydrogen ingress from the Gas Turbine Generator (GTG) H 2 cooler, identifying corrosion of carbon-steel surfaces under low-pH, low-dissolved-oxygen conditions as the source of H 2 evolution. The system was initially treated with ammonium hydroxide and carbohydrazide, which proved ineffective at preventing corrosion-related hydrogen generation under the prevailing operating conditions. To restore chemistry control, the plant implemented a transition to a nitrite-based corrosion-inhibition program consistent with Electric Power Research Institute (EPRI) guidance for closed-cycle cooling-water systems. Continuous monitoring showed sustained suppression during the monitoring period, with H 2 decreasing to zero within 29 days and remaining undetectable thereafter. The study provides a data-driven operating window—covering chemistry selection, dosing strategy, and monitoring frequency—that restores steady-state operation, prevents gas build-up, and maintains materials compatibility. The findings offer generalizable guidance for chemistry-based corrosion-risk control and reliable operation of industrial closed-cooling systems. • Hydrogen in GT-CCCW reduced from 1.6% to non-detect within 29 days • Corrosion-driven H 2 generation confirmed under low-pH and low-DO conditions • Nitrite-based inhibitor program effectively prevented corrosion-driven H 2 formation • Sustained H 2 suppression achieved with nitrite ≥500 ppm • Chemistry control demonstrated as a plant-scale safety and reliability measure

Authors

Institutions

Publication Details

Journal
Case Studies in Chemical and Environmental Engineering
Published
2026-04-22
DOI
https://doi.org/10.1016/j.cscee.2026.101388
Primary Topic
Thermodynamic and Exergetic Analyses of Power and Cooling Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Suppression of corrosion-driven hydrogen generation in gas turbine closed cooling water systems through transition from ammonium hydroxide–carbohydrazide to a nitrite-based inhibitor program

Ujjal Kumar Das, Md. Tawhidul Islam Khan, Khokon Mia
Case Studies in Chemical and Environmental Engineering
Thermodynamic and Exergetic Analyses of Power and Cooling Systems
article

Suppression of corrosion-driven hydrogen generation in gas turbine closed cooling water systems through transition from ammonium hydroxide–carbohydrazide to a nitrite-based inhibitor program

Ujjal Kumar Das, Md. Tawhidul Islam Khan, Khokon Mia
article en

Abstract

Reliable operation of closed cooling-water circuits in gas-turbine combined-cycle plants depends on appropriate cycle-chemistry design, monitoring, and control. This case study documents an engineered transition in the Gas Turbine Closed Circuit Cooling Water (GT-CCCW) system of a 414 MW combined-cycle power plant to eliminate corrosion-driven hydrogen (H 2 ) formation and stabilize operation, following the detection of significant hydrogen accumulation in the closed circuit, where gas-phase hydrogen concentrations measured after extraction reached an equivalent value of 16,035 mg L -1 (1.6%). Leak investigations confirmed no hydrogen ingress from the Gas Turbine Generator (GTG) H 2 cooler, identifying corrosion of carbon-steel surfaces under low-pH, low-dissolved-oxygen conditions as the source of H 2 evolution. The system was initially treated with ammonium hydroxide and carbohydrazide, which proved ineffective at preventing corrosion-related hydrogen generation under the prevailing operating conditions. To restore chemistry control, the plant implemented a transition to a nitrite-based corrosion-inhibition program consistent with Electric Power Research Institute (EPRI) guidance for closed-cycle cooling-water systems. Continuous monitoring showed sustained suppression during the monitoring period, with H 2 decreasing to zero within 29 days and remaining undetectable thereafter. The study provides a data-driven operating window—covering chemistry selection, dosing strategy, and monitoring frequency—that restores steady-state operation, prevents gas build-up, and maintains materials compatibility. The findings offer generalizable guidance for chemistry-based corrosion-risk control and reliable operation of industrial closed-cooling systems. • Hydrogen in GT-CCCW reduced from 1.6% to non-detect within 29 days • Corrosion-driven H 2 generation confirmed under low-pH and low-DO conditions • Nitrite-based inhibitor program effectively prevented corrosion-driven H 2 formation • Sustained H 2 suppression achieved with nitrite ≥500 ppm • Chemistry control demonstrated as a plant-scale safety and reliability measure

Case Studies in Chemical and Environmental EngineeringVol. 13
Babcock Power (United Kingdom) (GB)
Openalex Percentile: Top 10%
Thermodynamic and Exergetic Analyses of Power and Cooling Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.