Heat Transfer Rate, Effectiveness, and Pressure Drop Using Taguchi Method

This paper presents a systematic experimental investigation and optimisation of a shell-and-tube heat exchanger (STHE) performance using the Taguchi L9 orthogonal array and Analysis of Variance (ANOVA). Four operating parameters — shell-side flow rate, tube-side flow rate, inlet temperature difference, and baffle spacing — were investigated at three levels each. Response variables include heat transfer rate (Q), heat exchanger effectiveness (ε), and shell-side pressure drop (ΔP_s). Water was used as the working fluid on both sides. Signal-to-Noise ratio analysis identified the optimal parameter combination as shell-side flow rate 8 LPM, tube-side flow rate 12 LPM, inlet temperature difference 40°C, and baffle spacing 80 mm. ANOVA revealed tube-side flow rate as the most significant factor with 38.4 percent contribution to heat transfer rate, followed by inlet temperature difference (29.6 percent) and shell-side flow rate (22.8 percent). The optimal configuration achieved heat exchanger effectiveness ε = 0.784 and heat transfer rate Q = 4.82 kW — improvements of 41.6 percent and 38.2 percent respectively over the base condition. NTU-effectiveness method predictions agreed with experimental results within 7.1 percent. Confirmation experiments validated optimal values within 4.6 percent error.

Authors

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2026-04-20
DOI
https://doi.org/10.5281/zenodo.19663454
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Heat Transfer Rate, Effectiveness, and Pressure Drop Using Taguchi Method

V. M. Jamadar, P. P. Bhise Patole, A.D. Awasare
Zenodo (CERN European Organization for Nuclear Research)
Heat Transfer and Optimization
article

Heat Transfer Rate, Effectiveness, and Pressure Drop Using Taguchi Method

V. M. Jamadar, P. P. Bhise Patole, A.D. Awasare
article en

Abstract

This paper presents a systematic experimental investigation and optimisation of a shell-and-tube heat exchanger (STHE) performance using the Taguchi L9 orthogonal array and Analysis of Variance (ANOVA). Four operating parameters — shell-side flow rate, tube-side flow rate, inlet temperature difference, and baffle spacing — were investigated at three levels each. Response variables include heat transfer rate (Q), heat exchanger effectiveness (ε), and shell-side pressure drop (ΔP_s). Water was used as the working fluid on both sides. Signal-to-Noise ratio analysis identified the optimal parameter combination as shell-side flow rate 8 LPM, tube-side flow rate 12 LPM, inlet temperature difference 40°C, and baffle spacing 80 mm. ANOVA revealed tube-side flow rate as the most significant factor with 38.4 percent contribution to heat transfer rate, followed by inlet temperature difference (29.6 percent) and shell-side flow rate (22.8 percent). The optimal configuration achieved heat exchanger effectiveness ε = 0.784 and heat transfer rate Q = 4.82 kW — improvements of 41.6 percent and 38.2 percent respectively over the base condition. NTU-effectiveness method predictions agreed with experimental results within 7.1 percent. Confirmation experiments validated optimal values within 4.6 percent error.

Zenodo (CERN European Organization for Nuclear Research)
Affordable and clean energy
Openalex Percentile: Top 8%
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.