Robustness and performance analysis of a current-controlled quasi-stationary electrical model virtual synchronous machine using a parameter-dependent operating point

Ensuring stability in converter-dominated power systems requires voltage source converters to be robust under varying grid conditions and grid uncertainties such as short-circuit ratio variations. This paper analyzes the robustness of a grid-forming (GFM) current-controlled quasi-stationary electrical model virtual synchronous machine. We investigate the applicability of -analysis to systems incorporating GFM converters and demonstrate that operating point variations induced by parameter uncertainties must be explicitly considered. Due to the system's inherent nonlinearity, neglecting these variations can lead to misleading stability conclusions. To address the limitations of the -analysis, we introduce a robustness analysis method based on a parameter-dependent operating point and symbolic linearization, which enables efficient eigenvalue computation without repeated relinearization. Performance is additionally evaluated using sensitivity function analysis with respect to power reference tracking and angle disturbance rejection. The results show that appropriate control parameter selection improves robust stability under grid uncertainties by reducing undesired interactions.

Authors

Publication Details

Journal
TUHH Open Research
Published
2026-04-10
DOI
https://doi.org/10.15480/882.16992
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Robustness and performance analysis of a current-controlled quasi-stationary electrical model virtual synchronous machine using a parameter-dependent operating point

Francesco Giacomo Puricelli, Christina Zuromski, Jef Beerten, Christian Becker
TUHH Open Research
Microgrid Control and Optimization
article

Robustness and performance analysis of a current-controlled quasi-stationary electrical model virtual synchronous machine using a parameter-dependent operating point

Francesco Giacomo Puricelli, Christina Zuromski, Jef Beerten, Christian Becker
article en

Abstract

Ensuring stability in converter-dominated power systems requires voltage source converters to be robust under varying grid conditions and grid uncertainties such as short-circuit ratio variations. This paper analyzes the robustness of a grid-forming (GFM) current-controlled quasi-stationary electrical model virtual synchronous machine. We investigate the applicability of -analysis to systems incorporating GFM converters and demonstrate that operating point variations induced by parameter uncertainties must be explicitly considered. Due to the system's inherent nonlinearity, neglecting these variations can lead to misleading stability conclusions. To address the limitations of the -analysis, we introduce a robustness analysis method based on a parameter-dependent operating point and symbolic linearization, which enables efficient eigenvalue computation without repeated relinearization. Performance is additionally evaluated using sensitivity function analysis with respect to power reference tracking and angle disturbance rejection. The results show that appropriate control parameter selection improves robust stability under grid uncertainties by reducing undesired interactions.

TUHH Open Research
Affordable and clean energy
Openalex Percentile: Top 11%
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.