Numerical Investigation of Thermal and Hydraulic Performance for Grid-type Earth-to-Air Heat Exchangers: A Comparative Study of U-Type and Z-Type Configurations

Heating and cooling needs in greenhouses constitute a significant portion of total energy use, and therefore the adoption of passive and renewable approaches is important. Earth-to-air heat exchangers (EAHEs) exploit the relatively constant subsurface temperature to precondition ventilation air and may provide a sustainable option for greenhouse applications. Although grid-type configurations are particularly relevant to systems that require relatively large airflow rates, most previous studies have discussed isolated performance indicators under different geometrical and operating conditions, which makes fair comparison difficult. This study presents a numerical comparison of two grid-type EAHE configurations, Z-type and U-type, under identical geometric and operating conditions using four dimensionless performance parameters: thermal effectiveness ε, total pressure-loss coefficient K, airflow division uniformity coefficient Ω, and overall performance factor η* (defined as the ratio of heat-transfer rate to pumping power). The results show that the U-type layout improves flow distribution and reduces hydraulic losses. Ω increased from 0.79 to 0.87 for the U-type, while it decreased from 0.73 to 0.64 for the Z-type, resulting in a 38% improvement at high flow rates. Total pressure losses decreased by more than 28%, resulting in a corresponding reduction in fan-power demand. The thermal performance remained relatively similar, with ε differences ranging from 1% to 2%. However, η* was consistently higher for the U-type arrangement, exceeding the Z-type by more than 40% at the highest Reynolds number. Overall, the results suggest that the U-type EAHE provides the more favorable thermal–hydraulic performance for passive, energy-efficient greenhouse ventilation under the investigated conditions.

Authors

Publication Details

Journal
Journal of Engineering Research and Reports
Published
2026-04-15
DOI
https://doi.org/10.9734/jerr/2026/v28i41870
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Numerical Investigation of Thermal and Hydraulic Performance for Grid-type Earth-to-Air Heat Exchangers: A Comparative Study of U-Type and Z-Type Configurations

Mushtaq I. Hasan, Hussein L. Thamer
Journal of Engineering Research and Reports
Geothermal Energy Systems and Applications
article

Numerical Investigation of Thermal and Hydraulic Performance for Grid-type Earth-to-Air Heat Exchangers: A Comparative Study of U-Type and Z-Type Configurations

Mushtaq I. Hasan, Hussein L. Thamer
article en

Abstract

Heating and cooling needs in greenhouses constitute a significant portion of total energy use, and therefore the adoption of passive and renewable approaches is important. Earth-to-air heat exchangers (EAHEs) exploit the relatively constant subsurface temperature to precondition ventilation air and may provide a sustainable option for greenhouse applications. Although grid-type configurations are particularly relevant to systems that require relatively large airflow rates, most previous studies have discussed isolated performance indicators under different geometrical and operating conditions, which makes fair comparison difficult. This study presents a numerical comparison of two grid-type EAHE configurations, Z-type and U-type, under identical geometric and operating conditions using four dimensionless performance parameters: thermal effectiveness ε, total pressure-loss coefficient K, airflow division uniformity coefficient Ω, and overall performance factor η* (defined as the ratio of heat-transfer rate to pumping power). The results show that the U-type layout improves flow distribution and reduces hydraulic losses. Ω increased from 0.79 to 0.87 for the U-type, while it decreased from 0.73 to 0.64 for the Z-type, resulting in a 38% improvement at high flow rates. Total pressure losses decreased by more than 28%, resulting in a corresponding reduction in fan-power demand. The thermal performance remained relatively similar, with ε differences ranging from 1% to 2%. However, η* was consistently higher for the U-type arrangement, exceeding the Z-type by more than 40% at the highest Reynolds number. Overall, the results suggest that the U-type EAHE provides the more favorable thermal–hydraulic performance for passive, energy-efficient greenhouse ventilation under the investigated conditions.

Journal of Engineering Research and ReportsVol. 28(4)
Openalex Percentile: Top 32%
Geothermal Energy Systems and Applications
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.