Experimental investigation on thermal and moisture performance of direct evaporative cooling coupled with phase change plates for data centers

Direct evaporative cooling is widely used in data centers but risks elevating humidity. This study proposes a direct ventilation channel system integrating direct evaporative cooling with phase change plates. Experiments investigated effects of inlet air temperature (IAT: 28–44 °C), inlet relative humidity (IRH: 20–60%), air supply velocity (ASV: 1.0–3.0 m/s), and water flow (40–120 mL/min). Results show: (Ⅰ) The coupled system exhibits synergistic effects, achieving 31.43% cooling efficiency improvement as IAT increases from 28 °C to 44 °C. (Ⅱ) At IAT=36 °C and IRH=60%, outlet temperature reaches 27 °C with 62.3% RH, achieving 22% dehumidification rate. Dehumidification efficiency exceeds 18.8% for over 5 hours when IRH≥40%. (Ⅲ) Cooling performance factors order: IAT > ASV > IRH > WF, with IAT contributing 94.6%. Dehumidification factors order: IRH > IAT > ASV > WF, with IRH contributing 62.8% and IAT 23.9%. The system achieves EER up to 6.3 when meeting data center cooling demand (1728–3456 m 3 /h) at 30–32 °C. This study provides a feasible energy-saving cooling strategy for data centers.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2026-03-31
DOI
https://doi.org/10.1016/j.csite.2026.108000
Primary Topic
Adsorption and Cooling Systems
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental investigation on thermal and moisture performance of direct evaporative cooling coupled with phase change plates for data centers

Ruiyong Mao, Zujing Zhang, Jiri Zhou, H. Eric Xu et al.
Case Studies in Thermal Engineering
Adsorption and Cooling Systems
article

Experimental investigation on thermal and moisture performance of direct evaporative cooling coupled with phase change plates for data centers

Ruiyong Mao, Zujing Zhang, Jiri Zhou, H. Eric Xu, Yang Zhang, Xing Liang, Hongwei Wu
article en

Abstract

Direct evaporative cooling is widely used in data centers but risks elevating humidity. This study proposes a direct ventilation channel system integrating direct evaporative cooling with phase change plates. Experiments investigated effects of inlet air temperature (IAT: 28–44 °C), inlet relative humidity (IRH: 20–60%), air supply velocity (ASV: 1.0–3.0 m/s), and water flow (40–120 mL/min). Results show: (Ⅰ) The coupled system exhibits synergistic effects, achieving 31.43% cooling efficiency improvement as IAT increases from 28 °C to 44 °C. (Ⅱ) At IAT=36 °C and IRH=60%, outlet temperature reaches 27 °C with 62.3% RH, achieving 22% dehumidification rate. Dehumidification efficiency exceeds 18.8% for over 5 hours when IRH≥40%. (Ⅲ) Cooling performance factors order: IAT > ASV > IRH > WF, with IAT contributing 94.6%. Dehumidification factors order: IRH > IAT > ASV > WF, with IRH contributing 62.8% and IAT 23.9%. The system achieves EER up to 6.3 when meeting data center cooling demand (1728–3456 m 3 /h) at 30–32 °C. This study provides a feasible energy-saving cooling strategy for data centers.

Case Studies in Thermal EngineeringVol. 81
University of Hertfordshire (GB), Guizhou University (CN), Kingston University London (GB), China South Industries Group (China) (CN)
National Natural Science Foundation of China
Affordable and clean energy
Openalex Percentile: Top 38%
Adsorption and Cooling Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.