Evaluation of air cleaner effectiveness through experimental chamber testing and in-situ environmental assessment

The mass balance equation is utilized for theoretical analysis and experimental verification of the indoor PM2.5 concentration within residential buildings equipped with air cleaners. This study delves into the impact of various factors such as the positioning of air cleaners, Clean Air Delivery Rate (CADR), and the volume of the room on the non-uniform mixing model of air purification systems through meticulously designed experiments. Furthermore, an exponential function relationship between Effective Air Cleaning Ratio (EACR) and the air exchange rate of the air cleaner’s circulation is derived. When the air cleaner is positioned at the central position, the calculated EACR is 0.8. When placed against the wall, the calculation result is 0.76. In contrast, when situated in the corner, the indoor PM2.5 distribution is unbalanced due to the air flow delivered by the air cleaner, the EACR is only 0.74. To obtain the purification capacity of air cleaner in actual environments, an empirical correlation between EACR, room volume, and the nominal CADR is established based on experimental results. Practical application The placement of an air cleaner is a critical factor that directly influences its Clean Air Delivery Rate (CADR), resulting in a notable discrepancy between its laboratory-rated and actual performance for controlling indoor PM2.5 concentrations. The rated CADR value is insufficient for predicting actual removal effectiveness, the actual purification performance must account for practical room conditions, including room volume and airflow patterns. To obtain the purification capacity of air cleaner in actual environments, an empirical correlation between EACR, room volume, and the rated CADR is established based on experimental results. This study can provide a basis for effectively controlling indoor PM2.5 levels.

Authors

Institutions

Publication Details

Journal
Building Services Engineering Research and Technology
Published
2026-03-26
DOI
https://doi.org/10.1177/01436244261439548
Primary Topic
Indoor Air Quality and Microbial Exposure
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluation of air cleaner effectiveness through experimental chamber testing and in-situ environmental assessment

Ying Fan, Peng Hu, Wei Xie, Pengfei Si
Building Services Engineering Research and Technology
Indoor Air Quality and Microbial Exposure
article

Evaluation of air cleaner effectiveness through experimental chamber testing and in-situ environmental assessment

Ying Fan, Peng Hu, Wei Xie, Pengfei Si
article en

Abstract

The mass balance equation is utilized for theoretical analysis and experimental verification of the indoor PM2.5 concentration within residential buildings equipped with air cleaners. This study delves into the impact of various factors such as the positioning of air cleaners, Clean Air Delivery Rate (CADR), and the volume of the room on the non-uniform mixing model of air purification systems through meticulously designed experiments. Furthermore, an exponential function relationship between Effective Air Cleaning Ratio (EACR) and the air exchange rate of the air cleaner’s circulation is derived. When the air cleaner is positioned at the central position, the calculated EACR is 0.8. When placed against the wall, the calculation result is 0.76. In contrast, when situated in the corner, the indoor PM2.5 distribution is unbalanced due to the air flow delivered by the air cleaner, the EACR is only 0.74. To obtain the purification capacity of air cleaner in actual environments, an empirical correlation between EACR, room volume, and the nominal CADR is established based on experimental results. Practical application The placement of an air cleaner is a critical factor that directly influences its Clean Air Delivery Rate (CADR), resulting in a notable discrepancy between its laboratory-rated and actual performance for controlling indoor PM2.5 concentrations. The rated CADR value is insufficient for predicting actual removal effectiveness, the actual purification performance must account for practical room conditions, including room volume and airflow patterns. To obtain the purification capacity of air cleaner in actual environments, an empirical correlation between EACR, room volume, and the rated CADR is established based on experimental results. This study can provide a basis for effectively controlling indoor PM2.5 levels.

Building Services Engineering Research and Technology
Xi'an University of Architecture and Technology (CN), China Architecture Design & Research Group (China) (CN), Wenhua College, Huazhong University of Science and Technology (CN)
Openalex Percentile: Top 9%
Indoor Air Quality and Microbial Exposure
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.