Research on Pollutant Control and Thermal Environment Improvement in Underground Catering Spaces: A Case Study of the Catering Zone in a Commercial Complex

Air-conditioning and ventilation systems are conventional approaches to improving indoor thermal environments and removing pollutants in underground catering spaces. However, unsuitable system design leads to a degraded thermal environment and aggravated pollutant dispersion. This study combines onsite measurement and numerical simulation to investigate the optimization of entrance air curtains, exhaust air flowrates, and air-conditioning system in underground catering spaces. The onsite measurements revealed that average temperatures in the catering spaces ranged from 24.5 to 26.9 °C in summer and from 20.2 to 26.3 °C in winter, exceeding thermal comfort ranges in most areas. Additional aspects include the accumulation of contaminants, an ineffective entrance air curtain, and upward pollutant migration. Simulation results revealed that optimizing the entrance air curtains created a temperature difference exceeding 0.90 °C at the entrance and reduced PAH concentration in the semi-contaminated zone by over 96.0%. Adjusting the exhaust air flowrate enhanced the PAH removal but had limited influence on temperature. Adjusting air-conditioning parameters reduced entrance PAH by 99.7% and lowered the overall temperature and PAH concentration by 14.40% and 9.91%, respectively. Under a comprehensive optimization scheme integrating all three measures, airflow was directed from the clean zone to the contaminated zone. This scheme achieved average temperature reductions of 7.34% in summer and 13.58% in winter, reversing the PAH dispersion pathway and eliminating PAH in the semi-contaminated zone. The proposed scheme provides a practical engineering solution for thermal environment improvement and pollutant control in underground catering spaces, and offers a reference for the design of similar projects.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2026-03-01
DOI
https://doi.org/10.1016/j.csite.2026.107955
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on Pollutant Control and Thermal Environment Improvement in Underground Catering Spaces: A Case Study of the Catering Zone in a Commercial Complex

Tao Song, Yanqiu Huang, Fangfang Wei, Wenyang Wang et al.
Case Studies in Thermal Engineering
Refrigeration and Air Conditioning Technologies
article

Research on Pollutant Control and Thermal Environment Improvement in Underground Catering Spaces: A Case Study of the Catering Zone in a Commercial Complex

Tao Song, Yanqiu Huang, Fangfang Wei, Wenyang Wang, Jing Li
article en

Abstract

Air-conditioning and ventilation systems are conventional approaches to improving indoor thermal environments and removing pollutants in underground catering spaces. However, unsuitable system design leads to a degraded thermal environment and aggravated pollutant dispersion. This study combines onsite measurement and numerical simulation to investigate the optimization of entrance air curtains, exhaust air flowrates, and air-conditioning system in underground catering spaces. The onsite measurements revealed that average temperatures in the catering spaces ranged from 24.5 to 26.9 °C in summer and from 20.2 to 26.3 °C in winter, exceeding thermal comfort ranges in most areas. Additional aspects include the accumulation of contaminants, an ineffective entrance air curtain, and upward pollutant migration. Simulation results revealed that optimizing the entrance air curtains created a temperature difference exceeding 0.90 °C at the entrance and reduced PAH concentration in the semi-contaminated zone by over 96.0%. Adjusting the exhaust air flowrate enhanced the PAH removal but had limited influence on temperature. Adjusting air-conditioning parameters reduced entrance PAH by 99.7% and lowered the overall temperature and PAH concentration by 14.40% and 9.91%, respectively. Under a comprehensive optimization scheme integrating all three measures, airflow was directed from the clean zone to the contaminated zone. This scheme achieved average temperature reductions of 7.34% in summer and 13.58% in winter, reversing the PAH dispersion pathway and eliminating PAH in the semi-contaminated zone. The proposed scheme provides a practical engineering solution for thermal environment improvement and pollutant control in underground catering spaces, and offers a reference for the design of similar projects.

Case Studies in Thermal Engineering
Xi'an University of Architecture and Technology (CN), PLA Rocket Force University of Engineering (CN)
Openalex Percentile: Top 8%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.